Characterization of MV Instrument Transformers for Power Quality Measurement: the contribution from the IT4PQ project

The result's identifiers

  • Result code in IS VaVaI

    <a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F00177016%3A_____%2F24%3AN0000005" target="_blank" >RIV/00177016:_____/24:N0000005 - isvavai.cz</a>

  • Result on the web

    <a href="https://ieeexplore.ieee.org/document/10645830" target="_blank" >https://ieeexplore.ieee.org/document/10645830</a>

  • DOI - Digital Object Identifier

    <a href="http://dx.doi.org/10.1109/CPEM61406.2024.10645830" target="_blank" >10.1109/CPEM61406.2024.10645830</a>

Alternative languages

  • Result language

    angličtina

  • Original language name

    Characterization of MV Instrument Transformers for Power Quality Measurement: the contribution from the IT4PQ project

  • Original language description

    Power Quality (PQ) monitoring in electrical transmission and distribution grids relies on the accurate measurement of wideband high voltages and high currents. Ensuring traceability of the measurements carried out is generally only partially accomplished by calibration of the low voltage (LV) PQ measurement instrument, whereas the calibration of the instrument transformer (IT) is mostly limited to the power frequency or performed at LV. In the paper, objectives and main outputs of the research project “Measurement methods and test procedures for assessing accuracy of Instrument Transformers for Power Quality measurements” (IT4PQ), which is focused on medium voltage (MV) grids, are outlined. An overview of the metrological framework developed within IT4PQ is given, together with details of the characterization of different types of MV ITs, both under controlled laboratory conditions and in the presence of influence parameters. Laboratory calibration measurement uncertainty is within a few hundreds of ppm and microradian up to 9 kHz, for ratio and phase errors respectively.

  • Czech name

  • Czech description

Classification

  • Type

    D - Article in proceedings

  • CEP classification

  • OECD FORD branch

    20201 - Electrical and electronic engineering

Result continuities

  • Project

    <a href="/en/project/8B20011" target="_blank" >8B20011: Measurement methods and test procedures for assesing accuracy of instruments transformers for power quality measurements</a><br>

  • Continuities

    P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)

Others

  • Publication year

    2024

  • Confidentiality

    S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů

Data specific for result type

  • Article name in the collection

    2024 Conference on Precision Electromagnetic Measurements (CPEM)

  • ISBN

    979-8-3503-6104-9

  • ISSN

  • e-ISSN

  • Number of pages

    2

  • Pages from-to

  • Publisher name

  • Place of publication

    Denver, CO, USA

  • Event location

    Denver, CO, USA

  • Event date

    Jan 1, 2024

  • Type of event by nationality

    WRD - Celosvětová akce

  • UT code for WoS article

    001308252300005