Determination of Dehumidification Capacity of Water Wall with Controlled Water Temperature: Experimental Verification under Laboratory Conditions
The result's identifiers
Result code in IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F00216305%3A26110%2F21%3APU141243" target="_blank" >RIV/00216305:26110/21:PU141243 - isvavai.cz</a>
Result on the web
<a href="https://www.mdpi.com/2071-1050/13/10/5684" target="_blank" >https://www.mdpi.com/2071-1050/13/10/5684</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.3390/su13105684" target="_blank" >10.3390/su13105684</a>
Alternative languages
Result language
angličtina
Original language name
Determination of Dehumidification Capacity of Water Wall with Controlled Water Temperature: Experimental Verification under Laboratory Conditions
Original language description
Water elements with flowing water on the surface are common in buildings as a form of indoor decoration, and they are most often perceived as passive humidifiers. However, by controlling water temperature, they can be also used for air dehumidification. The dehumidification capacity of indoor water elements was investigated experimentally under laboratory conditions. For the experimental verification of dehumidification capacity, a water wall prototype with an effective area of falling water film of 1 m(2) and a measuring system were designed and developed. A total of 15 measurements were carried out with air temperatures ranging from 22.1 degrees C to 32.5 degrees C and relative humidity from 58.9% to 85.6%. The observed dehumidification capacity varied in the range of 21.99-315.36 g/h for the tested measurements. The results show that the condensation rate is a dynamic process, and the dehumidification capacity of a water wall strongly depends on indoor air parameters (air humidity and temperature). To determine the dehumidification capacity of a water wall for any boundary conditions, the equations were determined based on measured data, and two methods were used: the linear dependence between humidity ratio and condensation rate, and nonlinear surface fitting based on the dependence between the condensation rate, air temperature, and relative humidity.
Czech name
—
Czech description
—
Classification
Type
J<sub>imp</sub> - Article in a specialist periodical, which is included in the Web of Science database
CEP classification
—
OECD FORD branch
20101 - Civil engineering
Result continuities
Project
—
Continuities
O - Projekt operacniho programu
Others
Publication year
2021
Confidentiality
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Data specific for result type
Name of the periodical
Sustainability
ISSN
2071-1050
e-ISSN
—
Volume of the periodical
13
Issue of the periodical within the volume
10
Country of publishing house
CH - SWITZERLAND
Number of pages
17
Pages from-to
1-17
UT code for WoS article
000662558000001