Design of local ventilation for heat stress reduction of glass-making line operators
The result's identifiers
Result code in IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F00216305%3A26210%2F02%3APU34280" target="_blank" >RIV/00216305:26210/02:PU34280 - isvavai.cz</a>
Result on the web
—
DOI - Digital Object Identifier
—
Alternative languages
Result language
angličtina
Original language name
Design of local ventilation for heat stress reduction of glass-making line operators
Original language description
A distribution of locally supplied air to the working place of operators at the glass-making lines is designed so as not to affect the process of glass manufacture. The design of a local air supply is based on operational measurements of thermal conditions on the working place of operators. The measurements have been carried out at the natural ventilation and at application of the local air supply. The local air supply outlet was located either over the working place or on its floor. The analysis of opperators? heat stress was made by using the WBGT-index. From the measured WBGT-index dependence on the airflow velocity, the airflow velocities, which are needed for obtaining a homogenous environment with the WBGT reference value, have been determined. Thus defined courses of velocities along the working place height have been applied for the design of an optimum local air supply.
Czech name
—
Czech description
—
Classification
Type
D - Article in proceedings
CEP classification
BK - Liquid mechanics
OECD FORD branch
—
Result continuities
Project
<a href="/en/project/OC%20G3.20" target="_blank" >OC G3.20: Investigation of temperature fields in industrial buildings with various manners of ventilation and heating</a><br>
Continuities
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)<br>Z - Vyzkumny zamer (s odkazem do CEZ)
Others
Publication year
2002
Confidentiality
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Data specific for result type
Article name in the collection
Proceedings of 8th International Conference on Air Distribution in Rooms
ISBN
87-989117-0-8
ISSN
—
e-ISSN
—
Number of pages
4
Pages from-to
737-740
Publisher name
RoomVent 2002
Place of publication
Copenhagen, Denmark
Event location
Copenhagen
Event date
Sep 8, 2002
Type of event by nationality
WRD - Celosvětová akce