Capture efficiency measurement of local reinforced exhaust system
The result's identifiers
Result code in IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F00216305%3A26210%2F02%3APU34430" target="_blank" >RIV/00216305:26210/02:PU34430 - isvavai.cz</a>
Result on the web
—
DOI - Digital Object Identifier
—
Alternative languages
Result language
angličtina
Original language name
Capture efficiency measurement of local reinforced exhaust system
Original language description
This report deals with measurement of capture efficiency of the local reinforced exhaust system (REEXS). The constant ? emission tracer gas method is used for quantitative evaluation of capture efficiency. As a tracer gas was used carbon dioxide. Experimental equipment was supplemented by a special local exhaust hood. The local exhaust hood was designed in such way that it can work either as a traditional circular exhaust hood or as a REEXS. A characteristic of the REEXS principle is that the flow patteern may be oriented towards a specific direction, which increases the range of the efficient area significantly. The directional effect is created by radial air inlet along the edge of a flanged circular exhaust opening through a narrow slot. In this report are shown some results of experimental measurements. The measurements were done both for the traditional local exhaust hood and for the REEXS at different ratios between the momentum flow in the inlet and in the exhaust. All measureme
Czech name
—
Czech description
—
Classification
Type
D - Article in proceedings
CEP classification
BK - Liquid mechanics
OECD FORD branch
—
Result continuities
Project
<a href="/en/project/OC%20G3.50" target="_blank" >OC G3.50: Investigation of reinforced exhaust system</a><br>
Continuities
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)<br>Z - Vyzkumny zamer (s odkazem do CEZ)
Others
Publication year
2002
Confidentiality
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Data specific for result type
Article name in the collection
Proceedings of 8th International Conference on Air Distribution in Rooms
ISBN
87-989117-0-8
ISSN
—
e-ISSN
—
Number of pages
4
Pages from-to
681-684
Publisher name
RoomVent 2002
Place of publication
Copenhagen, Denmark
Event location
Copenhagen
Event date
Sep 8, 2002