Seasonal COP of an Air-to-Water Heat Pump when Using Predictive Control Preferring Power Production from Renewable Sources in the Czech Republic
The result's identifiers
Result code in IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F00216305%3A26210%2F19%3APU133025" target="_blank" >RIV/00216305:26210/19:PU133025 - isvavai.cz</a>
Result on the web
<a href="https://www.mdpi.com/1996-1073/12/17/3236" target="_blank" >https://www.mdpi.com/1996-1073/12/17/3236</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.3390/en12173236" target="_blank" >10.3390/en12173236</a>
Alternative languages
Result language
angličtina
Original language name
Seasonal COP of an Air-to-Water Heat Pump when Using Predictive Control Preferring Power Production from Renewable Sources in the Czech Republic
Original language description
The paper presents a parametric study evaluating the effects of various predictive controls on the operating parameters of heat pumps. The heat pump represents a significant power appliance in the residential sector. Its connection to the heat accumulator creates a system with considerable potential to control electricity consumption according to the needs of the electricity grid. The air-water heat pump is considered in this study. A predictive control is used for priority operation of the heat pump at periods of peak power production from renewable sources. The following were tested as the parameters of predictive control: outdoor air temperature, photovoltaic power production and wind power production. The combination of photovoltaic and wind power production was also tested. A parametric analysis considering different sizes for the thermal accumulator and the heating capacity of the heat pump were proposed. The benefits of predictive control are evaluated based on historical records of meteorological data from 2015 to 2018 in the city of Brno, Czech Republic. The data on the historical development of the real electrical energy production from renewable sources in the Czech Republic are used for regulation control in a monitored period. The main comparison parameter is the heat pump seasonal coefficient of performance (SCOP). From the carried out study results, an increase in SCOP by 14% was identified for priority operation of heat pump (HP ) at periods with highest outdoor air temperature. Priority operation of HP at periods with peak photovoltaic (PV) production increased SCOP by 10.25%. A decrease in SCOP only occurred in case with priority operation of HP at peak production of wind power plants. Increasing the size of the accumulator contributes to an increase in SCOP in all assessed modifications of predictive control.
Czech name
—
Czech description
—
Classification
Type
J<sub>imp</sub> - Article in a specialist periodical, which is included in the Web of Science database
CEP classification
—
OECD FORD branch
20704 - Energy and fuels
Result continuities
Project
<a href="/en/project/EF16_026%2F0008392" target="_blank" >EF16_026/0008392: Computer Simulations for Effective Low-Emission Energy Engineering</a><br>
Continuities
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)
Others
Publication year
2019
Confidentiality
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Data specific for result type
Name of the periodical
ENERGIES
ISSN
1996-1073
e-ISSN
—
Volume of the periodical
12
Issue of the periodical within the volume
3236
Country of publishing house
CH - SWITZERLAND
Number of pages
13
Pages from-to
1-13
UT code for WoS article
000486860500033
EID of the result in the Scopus database
2-s2.0-85071633073