The influence of plate corrugation geometry on heat and mass transfer performance of plate heat exchangers for condensation of steam in the presence of air
The result's identifiers
Result code in IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F00216305%3A26210%2F22%3APU143023" target="_blank" >RIV/00216305:26210/22:PU143023 - isvavai.cz</a>
Result on the web
<a href="https://www.sciencedirect.com/science/article/pii/S2451904922000555" target="_blank" >https://www.sciencedirect.com/science/article/pii/S2451904922000555</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.1016/j.tsep.2022.101248" target="_blank" >10.1016/j.tsep.2022.101248</a>
Alternative languages
Result language
angličtina
Original language name
The influence of plate corrugation geometry on heat and mass transfer performance of plate heat exchangers for condensation of steam in the presence of air
Original language description
Processes of steam condensation in the presence of air, as non-condensable gas, was studied in experiments with the models of plate heat exchanger (PHE) channels formed by plates with corrugations of different geometry. Validity of the developed mathematical model for the calculation of local process parameters is confirmed, and it is used to facilitate the analysis of experimental results. Sets of experiments were performed on five samples modelling PHE channel main corrugated field. The corrugations angle to plate vertical axis in three experimental samples was 30°, 45° and 60° at the same corrugations’ height of 5 mm. Another two samples had corrugations height 7.5 mm and 10 mm at the same corrugations angle 60°. Various effects of plate sizes and geometrical parameters of corrugations on the performance of PHE as a condenser for steam–air mixture and local process parameters profiles are discussed. Presented analysis shows that the specified process conditions on temperature and pressure drop in PHE can be satisfied by varying corrugations angle and channel spacing at plates of different lengths. To maintain the same temperature program with a decrease of plates corrugation angle from 60° to 30° require the plates with a length bigger from 2 to 2.6 times, depending on specific process conditions. These plate parameters are recommended for use as variables in solving the problem of PHE plate geometry optimisation with the use of the proposed mathematical model.
Czech name
—
Czech description
—
Classification
Type
J<sub>SC</sub> - Article in a specialist periodical, which is included in the SCOPUS database
CEP classification
—
OECD FORD branch
20704 - Energy and fuels
Result continuities
Project
<a href="/en/project/EF15_003%2F0000456" target="_blank" >EF15_003/0000456: Sustainable Process Integration Laboratory (SPIL)</a><br>
Continuities
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)
Others
Publication year
2022
Confidentiality
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Data specific for result type
Name of the periodical
Thermal science and engineering progress
ISSN
2451-9049
e-ISSN
—
Volume of the periodical
neuveden
Issue of the periodical within the volume
30
Country of publishing house
NL - THE KINGDOM OF THE NETHERLANDS
Number of pages
13
Pages from-to
101248-101248