Impedance Correction Factor of Three-Winding Transformers
The result's identifiers
Result code in IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F00216305%3A26220%2F10%3APU87880" target="_blank" >RIV/00216305:26220/10:PU87880 - isvavai.cz</a>
Result on the web
—
DOI - Digital Object Identifier
—
Alternative languages
Result language
angličtina
Original language name
Impedance Correction Factor of Three-Winding Transformers
Original language description
This paper focuses to using of impedance correction factor for three-winding transformers which is related to short-circuit voltage on referential power. This correction factor influence on size impedance is shown on the two examples of three-winding transformers and subsequently to the size of short-circuit current. The error of the short-circuit current can be made by conversion of the short-current voltage on another referential power and it can be even 19%. It is neccesary respect substitution at use computer program for calculation in nominal values.
Czech name
—
Czech description
—
Classification
Type
D - Article in proceedings
CEP classification
JE - Non-nuclear power engineering, energy consumption and utilization
OECD FORD branch
—
Result continuities
Project
—
Continuities
S - Specificky vyzkum na vysokych skolach
Others
Publication year
2010
Confidentiality
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Data specific for result type
Article name in the collection
Proceedings of the 16th Conference STUDENT EEICT 2010 Volume 4
ISBN
978-80-214-4079-1
ISSN
—
e-ISSN
—
Number of pages
250
Pages from-to
—
Publisher name
Vysoké učení technické v Brně
Place of publication
Brné
Event location
FEKT VUT v Brně
Event date
Apr 29, 2010
Type of event by nationality
CST - Celostátní akce
UT code for WoS article
—