Experimental Measuring of the Touch Voltages in Large Compensated Networks
The result's identifiers
Result code in IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F00216305%3A26220%2F12%3APU99437" target="_blank" >RIV/00216305:26220/12:PU99437 - isvavai.cz</a>
Result on the web
—
DOI - Digital Object Identifier
—
Alternative languages
Result language
angličtina
Original language name
Experimental Measuring of the Touch Voltages in Large Compensated Networks
Original language description
The paper describes the tests in real compensated distribution network with capacitive currents 300A and 800A. There were tested low-ohmic and arc fault. The first results show that the operation of large network is possible with using of the automaticsof additional earthing of affected phase. The touch and step voltages were reduced under level allowed by standard EN 50522.
Czech name
—
Czech description
—
Classification
Type
D - Article in proceedings
CEP classification
JE - Non-nuclear power engineering, energy consumption and utilization
OECD FORD branch
—
Result continuities
Project
<a href="/en/project/ED0014%2F01%2F01" target="_blank" >ED0014/01/01: Research and Technology Centre of Renewable Energy Sources</a><br>
Continuities
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)
Others
Publication year
2012
Confidentiality
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Data specific for result type
Article name in the collection
Proceedings of 2012 Electric Power Quality and Supply Reliability Conference
ISBN
978-1-4673-1978-2
ISSN
—
e-ISSN
—
Number of pages
319
Pages from-to
199-204
Publisher name
Tallin University of Technology
Place of publication
Tallin
Event location
Tartu
Event date
Jun 11, 2012
Type of event by nationality
WRD - Celosvětová akce
UT code for WoS article
000308528000033