Impact of distributed generation on power flows along parallelly operated MV feeders

The result's identifiers

  • Result code in IS VaVaI

    <a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F49777513%3A23220%2F18%3A43951510" target="_blank" >RIV/49777513:23220/18:43951510 - isvavai.cz</a>

  • Result on the web

    <a href="https://ieeexplore.ieee.org/document/8493640" target="_blank" >https://ieeexplore.ieee.org/document/8493640</a>

  • DOI - Digital Object Identifier

    <a href="http://dx.doi.org/10.1109/EEEIC.2018.8493640" target="_blank" >10.1109/EEEIC.2018.8493640</a>

Alternative languages

  • Result language

    angličtina

  • Original language name

    Impact of distributed generation on power flows along parallelly operated MV feeders

  • Original language description

    Medium voltage networks are usually operated in radial or open loop configuration. Temporary closed loop arrangement, used for load transferring without service interruption, is accompanied by the changes in power flows that result from the previous feeder loading and the difference in voltage phasors between supply substations. One of the potential operational problems is the insufficient interruption capability of sectionalizing switches to re-open the closed loop circuit. It depends on active and reactive power flows at the switch location. The simulation of interconnected primary feeders fed from different substations are performed to illustrate the impact of operational conditions, distributed generation of different capacities, different locations and different reactive power modes on active and reactive power flows, respectively current and its power factor in feeder sections. The interruption capability of common sectionalizing switches is assessed in order to show the potential operational constrains resulting from the requirement on safety reopening of closed loop circuit. Finally, the possible solutions to ensure the safety switching are discussed.

  • Czech name

  • Czech description

Classification

  • Type

    D - Article in proceedings

  • CEP classification

  • OECD FORD branch

    20201 - Electrical and electronic engineering

Result continuities

  • Project

  • Continuities

    S - Specificky vyzkum na vysokych skolach

Others

  • Publication year

    2018

  • Confidentiality

    S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů

Data specific for result type

  • Article name in the collection

    Conference Proceedings 2018 IEEE International Conference on Environment and Electrical Engineering and 2018 IEEE Industrial and Commercial Power Systems Europe (EEEIC /I&amp;CPS Europe)

  • ISBN

    978-1-5386-5186-5

  • ISSN

  • e-ISSN

    neuvedeno

  • Number of pages

    6

  • Pages from-to

    614-619

  • Publisher name

    IEEE

  • Place of publication

    Piscataway

  • Event location

    Palermo, Italy

  • Event date

    Jun 12, 2018

  • Type of event by nationality

    WRD - Celosvětová akce

  • UT code for WoS article

    000450163700011