Study of the necessity of use of virtual origin in assessment of selected Fire Plume characteristics

The result's identifiers

  • Result code in IS VaVaI

    <a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F61989100%3A27200%2F16%3A86098002" target="_blank" >RIV/61989100:27200/16:86098002 - isvavai.cz</a>

  • Alternative codes found

    RIV/61989100:27600/16:86098002

  • Result on the web

    <a href="https://www.researchgate.net/publication/310475169_Study_of_the_necessity_of_use_of_virtual_origin_in_assessment_of_selected_Fire_Plume_characteristics" target="_blank" >https://www.researchgate.net/publication/310475169_Study_of_the_necessity_of_use_of_virtual_origin_in_assessment_of_selected_Fire_Plume_characteristics</a>

  • DOI - Digital Object Identifier

    <a href="http://dx.doi.org/10.17973/MMSJ.2016_11_2016157" target="_blank" >10.17973/MMSJ.2016_11_2016157</a>

Alternative languages

  • Result language

    angličtina

  • Original language name

    Study of the necessity of use of virtual origin in assessment of selected Fire Plume characteristics

  • Original language description

    The introduction of this article describes the significance and characteristic of the Fire Plume virtual origin, which is used in the assessment of certain local fire parameters. Based on selected characteristics for determining the rising of axial temperature, gas flow rate and mass volume of smoke in a Fire Plume, the necessity of the use of virtual origin was assessed. The results were compared using selected statistical methods. The study was done for a fire thermal outputs from 1000 to 5000 kW and heights above the flammable material surface from 5 to 50 m. Based on the delimitation of deviation acceptability limits, where the variation coefficient value was selected up to 10% and the percentage deviation up to 15%, regression power and linear functions were derive, which, based on magnitude of the released heat flow, determine the minimal height above the fuel surface at which the Fire Plume virtual origin can be omitted under presumed conditions. At the same time, there are principles affecting the necessity of use of Fire Plume virtual origin in practical applications presented which may be designs of smoke and heat systems, respectively other fire safety equipment. (C) 2016, MM publishing Ltd. All rights reserved.

  • Czech name

  • Czech description

Classification

  • Type

    J<sub>x</sub> - Unclassified - Peer-reviewed scientific article (Jimp, Jsc and Jost)

  • CEP classification

    AQ - Safety and health protection, safety in operating machinery

  • OECD FORD branch

Result continuities

  • Project

    <a href="/en/project/VI20162019034" target="_blank" >VI20162019034: Research and development of validated models of fire and evacuation and their practical application in fire safety of buildings</a><br>

  • Continuities

    P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)

Others

  • Publication year

    2016

  • Confidentiality

    S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů

Data specific for result type

  • Name of the periodical

    MM Science Journal

  • ISSN

    1803-1269

  • e-ISSN

  • Volume of the periodical

    2016

  • Issue of the periodical within the volume

    NOVEMBER

  • Country of publishing house

    CZ - CZECH REPUBLIC

  • Number of pages

    5

  • Pages from-to

    1424-1428

  • UT code for WoS article

  • EID of the result in the Scopus database

    2-s2.0-84995581675