Flickermeter Comparison Test
The result's identifiers
Result code in IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F61989100%3A27240%2F13%3A86088815" target="_blank" >RIV/61989100:27240/13:86088815 - isvavai.cz</a>
Result on the web
—
DOI - Digital Object Identifier
—
Alternative languages
Result language
angličtina
Original language name
Flickermeter Comparison Test
Original language description
The paper describes the test of flicker evaluation made by eleven different types of power quality analyzers. The standard IEC 61000-4-15Ed.2 (Functional and design specification of flickermeter) issued on August 2010 specifies performance testing. Existing flickermeters from different manufacturers may provide different results when processing non-uniform voltage fluctuations. The flickermeters response to voltage varying signals with envelope shape typical for sawmill, heat pump, granulator was tested. Voltage fluctuation caused by operating of this electrical equipment was measured in the real low voltage distribution network by means of the power quality analyzer Topas 1000. One-period records of voltage fluctuation were available for the analysis.These were simulated on the programmable power voltage source HP6834B in the university lab.
Czech name
—
Czech description
—
Classification
Type
J<sub>x</sub> - Unclassified - Peer-reviewed scientific article (Jimp, Jsc and Jost)
CEP classification
JB - Sensors, detecting elements, measurement and regulation
OECD FORD branch
—
Result continuities
Project
—
Continuities
S - Specificky vyzkum na vysokych skolach
Others
Publication year
2013
Confidentiality
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Data specific for result type
Name of the periodical
Transactions on Electrical Engineering
ISSN
1805-3386
e-ISSN
—
Volume of the periodical
2
Issue of the periodical within the volume
1
Country of publishing house
CZ - CZECH REPUBLIC
Number of pages
4
Pages from-to
22-25