A multifunctional dynamic voltage restorer for power quality improvement
The result's identifiers
Result code in IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F61989100%3A27240%2F18%3A10239004" target="_blank" >RIV/61989100:27240/18:10239004 - isvavai.cz</a>
Alternative codes found
RIV/61989100:27730/18:10239004
Result on the web
<a href="http://dx.doi.org/10.3390/en11061351" target="_blank" >http://dx.doi.org/10.3390/en11061351</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.3390/en11061351" target="_blank" >10.3390/en11061351</a>
Alternative languages
Result language
angličtina
Original language name
A multifunctional dynamic voltage restorer for power quality improvement
Original language description
Power quality is a major concern in electrical power systems. The power quality disturbances such as sags, swells, harmonic distortion and other interruptions have an impact on the electrical devices and machines and in severe cases can cause serious damages. Therefore it is necessary to recognize and compensate all types of disturbances at an earliest time to ensure normal and efficient operation of the power system. To solve these problems, many types of power devices are used. At the present time, one of those devices, Dynamic Voltage Restorer (DVR) is the most efficient and effective device used in power distribution systems. In this paper, design and modeling of a new structure and a new control method of multifunctional DVRs for voltage quality correction are presented. The new control method was built in the stationary frame by combining Proportional Resonant controllers and Sequence-Decouple Resonant controllers. The performance of the device and this method under different conditions such as voltage swell, voltage sag due to symmetrical and unsymmetrical short circuit, starting of motors, and voltage distortion are described. Simulation result show the superior capability of the proposed DVR to improve power quality under different operating conditions and the effectiveness of the proposed method. The proposed new DVR controller is able to detect the voltage disturbances and control the converter to inject appropriate voltages independently for each phase and compensate to load voltage through three single-phase transformers.
Czech name
—
Czech description
—
Classification
Type
J<sub>imp</sub> - Article in a specialist periodical, which is included in the Web of Science database
CEP classification
—
OECD FORD branch
20201 - Electrical and electronic engineering
Result continuities
Project
<a href="/en/project/LO1404" target="_blank" >LO1404: Sustainable Development of Center ENET</a><br>
Continuities
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)<br>S - Specificky vyzkum na vysokych skolach
Others
Publication year
2018
Confidentiality
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Data specific for result type
Name of the periodical
Energies
ISSN
1996-1073
e-ISSN
—
Volume of the periodical
11
Issue of the periodical within the volume
6
Country of publishing house
CH - SWITZERLAND
Number of pages
17
Pages from-to
1-17
UT code for WoS article
000436552700029
EID of the result in the Scopus database
2-s2.0-85049251927