Improved protection scheme for shipboard microgrids based on high frequency impedance method with experimental validation

The result's identifiers

  • Result code in IS VaVaI

    <a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F62690094%3A18450%2F25%3A50022066" target="_blank" >RIV/62690094:18450/25:50022066 - isvavai.cz</a>

  • Result on the web

    <a href="https://www.sciencedirect.com/science/article/pii/S0142061524006732" target="_blank" >https://www.sciencedirect.com/science/article/pii/S0142061524006732</a>

  • DOI - Digital Object Identifier

    <a href="http://dx.doi.org/10.1016/j.ijepes.2024.110448" target="_blank" >10.1016/j.ijepes.2024.110448</a>

Alternative languages

  • Result language

    angličtina

  • Original language name

    Improved protection scheme for shipboard microgrids based on high frequency impedance method with experimental validation

  • Original language description

    his paper addresses the critical problem of fault detection in DC zonal shipboard microgrids, which is essential for ensuring system reliability and operational safety. The proposed method detects faults by utilizing the high-frequency characteristics of estimated impedance. The technique involves Fast Fourier Transform analysis of current and voltage waveforms to extract high-frequency components before and after a fault. These features help identify the system’s high-frequency impedance via a communication system. Fault detection is achieved by comparing the estimated impedance with a predefined threshold. The performance of the method is evaluated using MATLAB/Simulink simulations and experimental implementations under various scenarios. Communication between components in the DC zonal microgrid is managed using the IEC 61850 standard. Results demonstrate the method’s effectiveness in detecting faults under diverse conditions, including variations in fault resistance, dynamic load behavior, changes in photovoltaic irradiation, system configuration alterations, noise immunity, and multi-fault scenarios. The method achieves fault clearance times ranging from 0.17 ms in MATLAB/Simulink simulations to 33–45 ms in experimental tests, showing its capability to enhance fault detection in complex DC microgrid environments.

  • Czech name

  • Czech description

Classification

  • Type

    J<sub>imp</sub> - Article in a specialist periodical, which is included in the Web of Science database

  • CEP classification

  • OECD FORD branch

    20205 - Automation and control systems

Result continuities

  • Project

  • Continuities

    I - Institucionalni podpora na dlouhodoby koncepcni rozvoj vyzkumne organizace

Others

  • Publication year

    2025

  • Confidentiality

    S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů

Data specific for result type

  • Name of the periodical

    International Journal of Electrical Power &amp; Energy Systems

  • ISSN

    0142-0615

  • e-ISSN

    1879-3517

  • Volume of the periodical

    164

  • Issue of the periodical within the volume

    March

  • Country of publishing house

    GB - UNITED KINGDOM

  • Number of pages

    14

  • Pages from-to

    "Article number: 110448"

  • UT code for WoS article

    001423757400001

  • EID of the result in the Scopus database

    2-s2.0-85214237999