Experimental stand for measurement of characteristics of cooling tower components
The result's identifiers
Result code in IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F68407700%3A21220%2F19%3A00332094" target="_blank" >RIV/68407700:21220/19:00332094 - isvavai.cz</a>
Result on the web
—
DOI - Digital Object Identifier
—
Alternative languages
Result language
angličtina
Original language name
Experimental stand for measurement of characteristics of cooling tower components
Original language description
The experimental cooling tower is designed as an exhausted tower with a cross-section of 1.8 x 1.8 m. Tower height is 6m. The tower is located above the water channel located in the floor. The channel is 12m long, 1.5m wide and 1.6m deep. There is a collecting pool for catching cooled water under the tower. A spraying system consisting of a manifold and spray nozzles is located above the infill space. A total of 110 nozzles spaced across the tower were used in the tower. The nozzle attachment system allows for smooth regulation of the distance from fills. A droplet eliminator layer is placed above the spray nozzles and the tower continues to the vent line to the fan. Acceleration of air flow is solved by radial medium pressure fan. The tower is connected to this fan, whose power is 37kW and the maximum speed is 1.475 RPM. The air flow through the fan is 54.000 m3 / h at a static pressure of approx. 160 Pa. The tower was equipped with the following measuring technology: - Water flow - induction flow meter ELIS IS 1-111 - Water inlet temperature - measured by 4x Pt100 in the inlet pipe close to the nozzles - Outlet water temperature - measured by 3x Pt100 in the drain tank drain - Air flow - measured total difference (4x) with static (4x) pressure on the nozzle in the pipe downstream the fan - Air Inlet Temperature Measured by 4x Pt100 at Tower Entrance (4x Dry thermometer) - Humidity Input - 4x psychrometer (4x wet thermometer) - Output humidity - 2x psychrometer (4x dry thermometer, 2x wet thermometer) - Static pressure above fill - differential pressure transducer Rosemount + probe to 100% humidity.
Czech name
—
Czech description
—
Classification
Type
G<sub>funk</sub> - Functional sample
CEP classification
—
OECD FORD branch
20303 - Thermodynamics
Result continuities
Project
<a href="/en/project/TE01020036" target="_blank" >TE01020036: Advanced technologies for heat and electricity production</a><br>
Continuities
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)
Others
Publication year
2019
Confidentiality
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Data specific for result type
Internal product ID
FVZ 12112/01/2019
Numerical identification
OBJ2018-SL10000118
Technical parameters
Rozměr věže 1.8x1.8m, výška věže 6m, konstrukce vyrobena ze systému Alutec, výplně plexi 8mm + svařovaný PP. Odtah zajištěn radiálním ventilátorem 37kW s průtokem vzduchu 54 000 m3/h při statickém tlaku cca 160 Pa. Celková hmotnost zařízení 3800kg.
Economical parameters
Cena zařízení bez snímačů odhadnuta na 450 000Kč. Pro měření charakteristik bylo nutné osazení snímači tlaku, teploty, vlhkosti a průtoku v celkové ceně 320000Kč.