All

What are you looking for?

All
Projects
Results
Organizations

Quick search

  • Projects supported by TA ČR
  • Excellent projects
  • Projects with the highest public support
  • Current projects

Smart search

  • That is how I find a specific +word
  • That is how I leave the -word out of the results
  • “That is how I can find the whole phrase”

The energy saving potential of a rotary heat exchanger with bypass dampers

The result's identifiers

  • Result code in IS VaVaI

    <a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F68407700%3A21220%2F23%3A00364071" target="_blank" >RIV/68407700:21220/23:00364071 - isvavai.cz</a>

  • Result on the web

    <a href="https://doi.org/10.1016/j.enbuild.2023.112934" target="_blank" >https://doi.org/10.1016/j.enbuild.2023.112934</a>

  • DOI - Digital Object Identifier

    <a href="http://dx.doi.org/10.1016/j.enbuild.2023.112934" target="_blank" >10.1016/j.enbuild.2023.112934</a>

Alternative languages

  • Result language

    angličtina

  • Original language name

    The energy saving potential of a rotary heat exchanger with bypass dampers

  • Original language description

    The article deals with the possibilities of using a bypass damper in a rotary regenerative heat exchanger for heat recovery in ventilation and air conditioning system and calculates the energy savings related to overcoming the pressure loss of the exchanger. For the purposes of the analysis, a prototype heat exchanger with a wheel diameter of 1000 mm and bypass damper with a diameter of 200 mm was designed and constructed. The exchanger was subjected to an experimental investigation in order to determine its behaviour. The pressure loss of the exchanger, depending on the air flow rate, as well as the pressure loss for three nominal air flow rates, depending on the opening of the bypass damper, were measured. The measurement showed that the new exchanger design enables a reduction in the pressure loss of the exchanger by up to 49% compared to the original value. Based on the measured values, an analysis of the potential savings of electrical energy for driving fans in various European cities was carried out. The energy savings depend on the given climatic location where the exchanger will be used and on the operating time of the air handling unit. From the analyses carried out, it is clear that, by including the bypass damper, 18 to 44% of the electrical energy of the fan can be saved, which overcomes the pressure losses of the heat exchanger. Based on the current electricity prices, the return on the investment for the bypass damper was calculated based on the price of electricity at the given time and place (Prague - Czech Republic, 2022), which is from 0.5 to 3 years, depending on the type and period of operation of the air handling unit equipment, at common air velocities.

  • Czech name

  • Czech description

Classification

  • Type

    J<sub>imp</sub> - Article in a specialist periodical, which is included in the Web of Science database

  • CEP classification

  • OECD FORD branch

    20101 - Civil engineering

Result continuities

  • Project

    <a href="/en/project/TK02020006" target="_blank" >TK02020006: Increasing the Effectiveness of Rotary Regenerative Heat Exchangers</a><br>

  • Continuities

    P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)

Others

  • Publication year

    2023

  • Confidentiality

    S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů

Data specific for result type

  • Name of the periodical

    Energy and Buildings

  • ISSN

    0378-7788

  • e-ISSN

    1872-6178

  • Volume of the periodical

    285

  • Issue of the periodical within the volume

    3

  • Country of publishing house

    NL - THE KINGDOM OF THE NETHERLANDS

  • Number of pages

    14

  • Pages from-to

  • UT code for WoS article

    000950327700001

  • EID of the result in the Scopus database

    2-s2.0-85150840368