Weak Points of Current Sensors in Static Energy Meters
The result's identifiers
Result code in IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F68407700%3A21230%2F10%3A00175282" target="_blank" >RIV/68407700:21230/10:00175282 - isvavai.cz</a>
Result on the web
—
DOI - Digital Object Identifier
—
Alternative languages
Result language
angličtina
Original language name
Weak Points of Current Sensors in Static Energy Meters
Original language description
The energy meters with dual core current transformers, that measure energy consumption of inductive or capacitive load and DC magnetic flux is present in the core, measure with the errors up to few tens of percentage. It is due to saturation of high permeability and it causes the step change of phase displacement. This change in dependence on the distance between permanent magnet and current transformer can be up to tens of degrees. The article deals with these errors and shows them in dependence on thetype of load.
Czech name
—
Czech description
—
Classification
Type
J<sub>x</sub> - Unclassified - Peer-reviewed scientific article (Jimp, Jsc and Jost)
CEP classification
JB - Sensors, detecting elements, measurement and regulation
OECD FORD branch
—
Result continuities
Project
—
Continuities
Z - Vyzkumny zamer (s odkazem do CEZ)
Others
Publication year
2010
Confidentiality
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Data specific for result type
Name of the periodical
Journal of Electrical Engineering
ISSN
1335-3632
e-ISSN
—
Volume of the periodical
61
Issue of the periodical within the volume
7/s
Country of publishing house
SK - SLOVAKIA
Number of pages
4
Pages from-to
—
UT code for WoS article
—
EID of the result in the Scopus database
—