Verification of Partial Discharge Calibrators
The result's identifiers
Result code in IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F68407700%3A21230%2F13%3A00207075" target="_blank" >RIV/68407700:21230/13:00207075 - isvavai.cz</a>
Result on the web
—
DOI - Digital Object Identifier
—
Alternative languages
Result language
angličtina
Original language name
Verification of Partial Discharge Calibrators
Original language description
The paper deals with an impulse charge measurement in the range from few pC to tens of nC with higher accuracy. An impulse charge is usually generated by calibrators of partial discharge measurement instruments. The charge value is determined from recorded impulse current as voltage drop on sensing resistor, which loads the calibrator. The resulted charge, which is generated by calibrator, is then evaluated as numerical integration of impulse current. Some results of numerical integration using digitalscope and direct sampling by 14-bits digitizer with sampling frequency of 200 MSa/s are presented in the text. The investigation of measurement uncertainty is presented as well.
Czech name
—
Czech description
—
Classification
Type
D - Article in proceedings
CEP classification
JB - Sensors, detecting elements, measurement and regulation
OECD FORD branch
—
Result continuities
Project
—
Continuities
S - Specificky vyzkum na vysokych skolach
Others
Publication year
2013
Confidentiality
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Data specific for result type
Article name in the collection
Applied Electronics - 2013 International Conference on Applied Electronics
ISBN
978-80-261-0166-6
ISSN
1803-7232
e-ISSN
—
Number of pages
3
Pages from-to
229-231
Publisher name
University of West Bohemia
Place of publication
Pilsen
Event location
Pilsen
Event date
Sep 10, 2013
Type of event by nationality
EUR - Evropská akce