Evaluation of the Effect of Tube Pitch and Surface Alterations on Temperature Field at Sprinkled Tube Bundle
The result's identifiers
Result code in IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F00216305%3A26210%2F15%3APU111362" target="_blank" >RIV/00216305:26210/15:PU111362 - isvavai.cz</a>
Result on the web
<a href="http://dx.doi.org/10.1051/epjconf/20159202039" target="_blank" >http://dx.doi.org/10.1051/epjconf/20159202039</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.1051/epjconf/20159202039" target="_blank" >10.1051/epjconf/20159202039</a>
Alternative languages
Result language
angličtina
Original language name
Evaluation of the Effect of Tube Pitch and Surface Alterations on Temperature Field at Sprinkled Tube Bundle
Original language description
Water flowing on a sprinkled tube bundle forms three basic modes: It is the Droplet mode (liquid drips from one tube to another), the Jet mode (with an increasing flow rate droplets merge into a column) and the Membrane (Sheet) mode (with further increasing of falling film liquid flow rate columns merge and create sheets between the tubes. With sufficient flow rate sheets merge at this state and the tube bundle is completely covered by a thin liquid film). There are several factors influencing the individual mode types as well as heat transfer. Beside the above mentioned falling film liquid flow rate they are for instance tube diameters, tube pitches in a tube bundle or a physical condition of a falling film liquid. This paper presents a summary of data measured at atmospheric pressure at a tube bundle consisting of copper tubes of 12 milimeters diameter and of the studied tube length one meter. The tubes are positioned horizontally one above another with the tested pitches of 15, 20, 25 and 30 mm and there is a distribution tube placed above them with water flowing out. The thermal gradient of 15–40 has been tested with all pitches where the falling film liquid's temperature at the inlet of the distribution tube was 15 deg.C. The liquid was heated during the flow through the exchanger and the temperature of the sprinkled (heater) liquid at the inlet of the exchanger with a constant flow rate about 7.2 litres per minute was 40 deg.C. The tested flow of the falling film liquid ranged from 1.0 to 13.0 litres per minute. Sequences of 180 exposures have been recorded in partial flow rate stages by thermographic camera with record frequency of 30 Hz which were consequently assessed using the Matlab programme. This paper presents results achieved at the above mentioned pitches and at three types of tube bundle surfaces.
Czech name
—
Czech description
—
Classification
Type
D - Article in proceedings
CEP classification
—
OECD FORD branch
20704 - Energy and fuels
Result continuities
Project
<a href="/en/project/LO1202" target="_blank" >LO1202: NETME CENTRE PLUS</a><br>
Continuities
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)<br>S - Specificky vyzkum na vysokych skolach
Others
Publication year
2015
Confidentiality
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Data specific for result type
Article name in the collection
EPJ Web of Conferences
ISBN
—
ISSN
2100-014X
e-ISSN
—
Number of pages
8
Pages from-to
1-8
Publisher name
EDP Sciences
Place of publication
Francie
Event location
Český Krumlov
Event date
Nov 18, 2014
Type of event by nationality
WRD - Celosvětová akce
UT code for WoS article
000358249900041