Effect of Tube Pitch on Heat Transfer in Sprinkled Tube Bundle

The result's identifiers

  • Result code in IS VaVaI

    <a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F00216305%3A26210%2F15%3APU116015" target="_blank" >RIV/00216305:26210/15:PU116015 - isvavai.cz</a>

  • Result on the web

    <a href="http://dx.doi.org/10.14311/AP.2015.55.0329" target="_blank" >http://dx.doi.org/10.14311/AP.2015.55.0329</a>

  • DOI - Digital Object Identifier

    <a href="http://dx.doi.org/10.14311/AP.2015.55.0329" target="_blank" >10.14311/AP.2015.55.0329</a>

Alternative languages

  • Result language

    angličtina

  • Original language name

    Effect of Tube Pitch on Heat Transfer in Sprinkled Tube Bundle

  • Original language description

    Water flowing on a sprinkled tube bundle forms three basic modes: the Droplet mode (the liquid drips from one tube to another), the Jet mode (with an increasing flow rate, the droplets merge into a column) and the Membrane (Sheet) mode (with a further increase in the flow rate of the falling film liquid, the columns merge and create sheets between the tubes. With a sufficient flow rate, the sheets merge at this stage, and the tube bundle is completely covered by a thin liquid film). There are several factors influencing both the individual modes and the heat transfer. Beside the above-mentioned falling film liquid flow rate, these are for instance the tube diameters, the tube pitches in the tube bundle, or the physical conditions of the falling film liquid. This paper presents a summary of data measured at atmospheric pressure, with a tube bundle consisting of copper tubes of 12 millimetres in diameter, and with a studied tube length of one meter. The tubes are situated horizontally one above another at a pitch of 15 to 30 mm, and there is a distribution tube placed above them with water flowing through apertures of 1.0mm in diameter at a 9.2mm span. Two thermal conditions have been tested with all pitches: 15 °C to 40 °C and 15 °C to 45 °C. The temperature of the falling film liquid, which was heated during the flow through the exchanger, was 15 °C at the distribution tube input. The temperature of the heating liquid at the exchanger input, which had a constant flow rate of approx. 7.2. litres per minute, was 40 °C, or alternatively 45 °C.

  • Czech name

  • Czech description

Classification

  • Type

    J<sub>imp</sub> - Article in a specialist periodical, which is included in the Web of Science database

  • CEP classification

  • OECD FORD branch

    20704 - Energy and fuels

Result continuities

  • Project

    <a href="/en/project/LO1202" target="_blank" >LO1202: NETME CENTRE PLUS</a><br>

  • Continuities

    P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)

Others

  • Publication year

    2015

  • Confidentiality

    S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů

Data specific for result type

  • Name of the periodical

    Acta Polytechnica

  • ISSN

    1210-2709

  • e-ISSN

    1805-2363

  • Volume of the periodical

    55

  • Issue of the periodical within the volume

    5

  • Country of publishing house

    CZ - CZECH REPUBLIC

  • Number of pages

    6

  • Pages from-to

    329-334

  • UT code for WoS article

    000433701100007

  • EID of the result in the Scopus database

    2-s2.0-84946040529