FOULING OF POLYMERIC HOLLOW FIBER HEAT EXCHANGER BY ASHRAE 52.1 TEST DUST
The result's identifiers
Result code in IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F00216305%3A26210%2F17%3APU124185" target="_blank" >RIV/00216305:26210/17:PU124185 - isvavai.cz</a>
Result on the web
—
DOI - Digital Object Identifier
—
Alternative languages
Result language
angličtina
Original language name
FOULING OF POLYMERIC HOLLOW FIBER HEAT EXCHANGER BY ASHRAE 52.1 TEST DUST
Original language description
Thermal effectiveness of heat exchangers working in contaminated conditions is negatively affected by fouling. Considering HVAC-R (heating, ventilation and air conditioning) or automotive applications, outdoor or domestic dust can be defined as main source of fouling. The heat exchanger made of polymeric hollow fibers was designed and tested in conditions typical for indoor fancoil operation, namely room temperature air (20 °C) flowing through the hot water coil (water inlet 50 °C) with low velocity (1.5 m/s). ASHRAE test dust was used as recommended type of foulant to model domestic dust presence. It was found that the ASHRAE Dust 52.1 has a very significant impact on the pressure drop and heat transfer. Air-side pressure drop rises 191% and overall heat transfer coefficient decreased to 62% for a dust injection of 250g (4000 g/m2). Decrease of heat transfer rate of heat exchanger was influenced mainly by clogging the frontal area because the first layers were significantly more than deeper layers. S
Czech name
—
Czech description
—
Classification
Type
O - Miscellaneous
CEP classification
—
OECD FORD branch
20303 - Thermodynamics
Result continuities
Project
Result was created during the realization of more than one project. More information in the Projects tab.
Continuities
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)
Others
Publication year
2017
Confidentiality
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů