An effect of a wide area compensated distribution network operation to touch voltage at the point of DTS which is connected to LV earthing system
The result's identifiers
Result code in IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F00216305%3A26220%2F11%3APU95094" target="_blank" >RIV/00216305:26220/11:PU95094 - isvavai.cz</a>
Result on the web
—
DOI - Digital Object Identifier
—
Alternative languages
Result language
čeština
Original language name
Vliv provozu kompenzované sítě velkého rozsahu na velikost dotykového napětí u DTS se společným uzemněním
Original language description
This contribution is focused on evaluation of touch voltage quantity during a permanent ground fault in compensated distribution network with wide size of capacitive current 812 A. The touch voltage was evaluated near distribution transformer station 22/0.4 kV with the earthing system interconnected with the earthing of the neutral conductor of the LV network (0.4 kV). The data were recorded during real experiment, where low-impedance and arcing ground faults occurred. The fault was performed by conductive connection between faulty phase and iron part of the station which is connected to its earthing system. In this case, the fault current could achieve maximum quantity. (Influence of compensated distribution network operation with wide range on a touch voltage)
Czech name
Vliv provozu kompenzované sítě velkého rozsahu na velikost dotykového napětí u DTS se společným uzemněním
Czech description
This contribution is focused on evaluation of touch voltage quantity during a permanent ground fault in compensated distribution network with wide size of capacitive current 812 A. The touch voltage was evaluated near distribution transformer station 22/0.4 kV with the earthing system interconnected with the earthing of the neutral conductor of the LV network (0.4 kV). The data were recorded during real experiment, where low-impedance and arcing ground faults occurred. The fault was performed by conductive connection between faulty phase and iron part of the station which is connected to its earthing system. In this case, the fault current could achieve maximum quantity. (Influence of compensated distribution network operation with wide range on a touch voltage)
Classification
Type
D - Article in proceedings
CEP classification
JE - Non-nuclear power engineering, energy consumption and utilization
OECD FORD branch
—
Result continuities
Project
<a href="/en/project/ED0014%2F01%2F01" target="_blank" >ED0014/01/01: Research and Technology Centre of Renewable Energy Sources</a><br>
Continuities
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)<br>S - Specificky vyzkum na vysokych skolach
Others
Publication year
2011
Confidentiality
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Data specific for result type
Article name in the collection
Proceedings of the 6th International Scientific Symposium on Electrical Power Engineering Elektroenergetika 2011
ISBN
978-80-553-0724-4
ISSN
—
e-ISSN
—
Number of pages
5
Pages from-to
253-257
Publisher name
Technická univerzita Košice, Katedra elektroenergetiky
Place of publication
Mäsiarska 74 042 00 Košice
Event location
Stará Lesná
Event date
Sep 21, 2011
Type of event by nationality
EUR - Evropská akce
UT code for WoS article
—