Model-based control system design for steam turbine based on Functional Mock-up interface (FMI/FMU)

The result's identifiers

  • Result code in IS VaVaI

    <a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F49777513%3A23520%2F18%3A43952477" target="_blank" >RIV/49777513:23520/18:43952477 - isvavai.cz</a>

  • Result on the web

    <a href="https://ieeexplore.ieee.org/stamp/stamp.jsp?tp=&arnumber=8399693" target="_blank" >https://ieeexplore.ieee.org/stamp/stamp.jsp?tp=&arnumber=8399693</a>

  • DOI - Digital Object Identifier

    <a href="http://dx.doi.org/10.1109/CarpathianCC.2018.8399693" target="_blank" >10.1109/CarpathianCC.2018.8399693</a>

Alternative languages

  • Result language

    angličtina

  • Original language name

    Model-based control system design for steam turbine based on Functional Mock-up interface (FMI/FMU)

  • Original language description

    This paper exploits the authors recent work where real-time simulator of the steam turbine was developed using mathematical-physical modeling. Consequently, this work focuses on exact feedback controller design. Firstly, the steam turbine model was linearized for operations in the so-called island and national grid mode. Further, the generalized robustness regions method was applied to design 2DOF PI/PID controller for both working modes. Fulfilling design requirements (sensitivity function limits, gain and phase margins) ensures the required robustness of feedback loop. Using export to FMU (Functional Mock-up Unit), the resulted controller was validated in real-time in both SiL (Software-in-the-Loop) and HiL (Hardware-in-the-Loop) schemes. The presented procedure allows rapid optimization/re-tuning/adaptation of controller in case the model is changed. It is supposed that similar procedure will be applied on other energetic devices (water turbine, power generator, drum boiler, etc.).

  • Czech name

  • Czech description

Classification

  • Type

    D - Article in proceedings

  • CEP classification

  • OECD FORD branch

    20205 - Automation and control systems

Result continuities

  • Project

    <a href="/en/project/LO1506" target="_blank" >LO1506: Sustainability support of the centre NTIS - New Technologies for the Information Society</a><br>

  • Continuities

    P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)

Others

  • Publication year

    2018

  • Confidentiality

    S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů

Data specific for result type

  • Article name in the collection

    2018 19th International Carpathian Control Conference

  • ISBN

    978-1-5386-4762-2

  • ISSN

    neuvedeno

  • e-ISSN

    neuvedeno

  • Number of pages

    6

  • Pages from-to

    559-564

  • Publisher name

    IEEE

  • Place of publication

    Danvers

  • Event location

    Szilvasvarad, Hungary

  • Event date

    May 28, 2018

  • Type of event by nationality

    WRD - Celosvětová akce

  • UT code for WoS article

    000439260500104