Analysis of Output Signal Distortion of Galvanic Isolation Circuits for Monitoring the Mains Voltage Waveform

The result's identifiers

  • Result code in IS VaVaI

    <a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F60460709%3A41310%2F22%3A91722" target="_blank" >RIV/60460709:41310/22:91722 - isvavai.cz</a>

  • Result on the web

    <a href="https://www.mdpi.com/1424-8220/22/20/7769" target="_blank" >https://www.mdpi.com/1424-8220/22/20/7769</a>

  • DOI - Digital Object Identifier

    <a href="http://dx.doi.org/10.3390/s22207769" target="_blank" >10.3390/s22207769</a>

Alternative languages

  • Result language

    angličtina

  • Original language name

    Analysis of Output Signal Distortion of Galvanic Isolation Circuits for Monitoring the Mains Voltage Waveform

  • Original language description

    Different methods for galvanically isolated monitoring of the mains voltage waveform were evaluated. The aim was to determine the level of distortion of the output signal relative to the input signal and the suitability of each method for calculating active power values. Six fixtures were tested: two voltage transformers, an electronic circuit with a current transformer, a standalone current transformer, a simple circuit with optocouplers, and a circuit with an A/D-D/A converter with capacitive coupling. The input and output waveforms were mathematically analyzed by three methods: (1) calculating the spectral components of waveforms and the relative changes in their THD (total harmonic distortion) values, (2) determining the similarity of waveforms according to the size of the area bounded by the input and output waveform curves, and (3) determining the accuracy of the active power calculation based on the output waveform. The time difference in the zero crossing of the input and output signals was m

  • Czech name

  • Czech description

Classification

  • Type

    J<sub>imp</sub> - Article in a specialist periodical, which is included in the Web of Science database

  • CEP classification

  • OECD FORD branch

    20704 - Energy and fuels

Result continuities

  • Project

  • Continuities

    S - Specificky vyzkum na vysokych skolach

Others

  • Publication year

    2022

  • Confidentiality

    S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů

Data specific for result type

  • Name of the periodical

    SENSORS

  • ISSN

    1424-8220

  • e-ISSN

    1424-8220

  • Volume of the periodical

    22

  • Issue of the periodical within the volume

    20

  • Country of publishing house

    CZ - CZECH REPUBLIC

  • Number of pages

    20

  • Pages from-to

    1-20

  • UT code for WoS article

    000873700500001