Removal of Corrosive Sulfur from Insulating Oils by Natural Sorbent and Liquid-Liquid.

The result's identifiers

  • Result code in IS VaVaI

    <a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F67985858%3A_____%2F17%3A00477159" target="_blank" >RIV/67985858:_____/17:00477159 - isvavai.cz</a>

  • Result on the web

    <a href="http://dx.doi.org/10.1109/TDEI.2017.006660" target="_blank" >http://dx.doi.org/10.1109/TDEI.2017.006660</a>

  • DOI - Digital Object Identifier

    <a href="http://dx.doi.org/10.1109/TDEI.2017.006660" target="_blank" >10.1109/TDEI.2017.006660</a>

Alternative languages

  • Result language

    angličtina

  • Original language name

    Removal of Corrosive Sulfur from Insulating Oils by Natural Sorbent and Liquid-Liquid.

  • Original language description

    Prevention of energy transformer failures by removing so-called corrosive sulfur from insulation oil belongs to the most important tasks. This article is focused on finding an effective way suitable for decontamination of mineral insulation oils containing sulfur compounds together with regeneration of the insulation oils. Two methods were suggested and optimized, sorption technique on the newly suggested natural sorbents, bentonites, and liquid-liquid extraction with subsequent sorption. The effectiveness of proposed methods was compared with the common technique of filtration through a layer of commercially available Fuller’s earth. The real insulation oil from transformers with relatively high content of dibenzyl disulfide - 71.6 mg kg-1 was applied in all tests. Both suggested methods revealed a high efficiency of a corrosive sulfur removal and both bentonites possessed significantly better sorption properties than the commercial regenerated Fuller’s earth. Moreover, technological characteristics of regenerated oils by both methods met all requirements of the standards no. CSN EN 60422 and their properties corresponded to the new electro-insulation oils.

  • Czech name

  • Czech description

Classification

  • Type

    J<sub>imp</sub> - Article in a specialist periodical, which is included in the Web of Science database

  • CEP classification

  • OECD FORD branch

    20402 - Chemical process engineering

Result continuities

  • Project

    <a href="/en/project/TA04020151" target="_blank" >TA04020151: Enhancement of the power transformer operation security and prevention of their failures caused by the corrosive sulphur effect</a><br>

  • Continuities

    I - Institucionalni podpora na dlouhodoby koncepcni rozvoj vyzkumne organizace

Others

  • Publication year

    2017

  • Confidentiality

    S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů

Data specific for result type

  • Name of the periodical

    IEEE Transactions on Dielectrics and Electrical Insulation

  • ISSN

    1070-9878

  • e-ISSN

  • Volume of the periodical

    24

  • Issue of the periodical within the volume

    4

  • Country of publishing house

    US - UNITED STATES

  • Number of pages

    7

  • Pages from-to

    2383-2389

  • UT code for WoS article

    000411003700051

  • EID of the result in the Scopus database

    2-s2.0-85029786423