A comparative study on the applicability of six radiant floor, wall, and ceiling heating systems based on thermal performance analysis
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F00216305%3A26110%2F21%3APU140892" target="_blank" >RIV/00216305:26110/21:PU140892 - isvavai.cz</a>
Výsledek na webu
<a href="https://www.sciencedirect.com/science/article/pii/S2352710220337657?via%3Dihub#gs2" target="_blank" >https://www.sciencedirect.com/science/article/pii/S2352710220337657?via%3Dihub#gs2</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.1016/j.jobe.2020.102133" target="_blank" >10.1016/j.jobe.2020.102133</a>
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
A comparative study on the applicability of six radiant floor, wall, and ceiling heating systems based on thermal performance analysis
Popis výsledku v původním jazyce
Holistic comparisons of radiant heating systems that would help make an informed decision on the selection of the most convenient system for the specific application are lacking. The applicability of six representative radiant floor, wall, and ceiling heating systems was therefore compared in terms of thermal output and surface area required, controllability, short-term and long-term heat storage, suitability for building retrofit, and investments. Temperature and heat flux distribution in the structure, time constant tau(63), response time tau(90), and the number of operating cycles were computed by a custom-made and verified software tool using the finite volume method. Thermal energy stored was used to determine the ability of energy storage, whereas investment costs indicated affordability. Wall heating with pipes attached to a thermally insulating core had the highest thermal output, was easy to control, suitable for building retrofit, and most affordable while providing limited thermal storage. The performance of the wall system was retained when locating the pipes in plasterboard separated from the core by an air gap. Floor heating performed consistently in all the aspects evaluated. It was demonstrated that inserting a metal fin between pipes and the concrete spread layer improved thermal output, controllability, and storage capacity of the floor system with minor effect on investments. Ceiling with pipes insulated from the core performed well when thermal storage was not required. Ceiling with pipes embedded in the core was only feasible when long-term heat storage was needed.
Název v anglickém jazyce
A comparative study on the applicability of six radiant floor, wall, and ceiling heating systems based on thermal performance analysis
Popis výsledku anglicky
Holistic comparisons of radiant heating systems that would help make an informed decision on the selection of the most convenient system for the specific application are lacking. The applicability of six representative radiant floor, wall, and ceiling heating systems was therefore compared in terms of thermal output and surface area required, controllability, short-term and long-term heat storage, suitability for building retrofit, and investments. Temperature and heat flux distribution in the structure, time constant tau(63), response time tau(90), and the number of operating cycles were computed by a custom-made and verified software tool using the finite volume method. Thermal energy stored was used to determine the ability of energy storage, whereas investment costs indicated affordability. Wall heating with pipes attached to a thermally insulating core had the highest thermal output, was easy to control, suitable for building retrofit, and most affordable while providing limited thermal storage. The performance of the wall system was retained when locating the pipes in plasterboard separated from the core by an air gap. Floor heating performed consistently in all the aspects evaluated. It was demonstrated that inserting a metal fin between pipes and the concrete spread layer improved thermal output, controllability, and storage capacity of the floor system with minor effect on investments. Ceiling with pipes insulated from the core performed well when thermal storage was not required. Ceiling with pipes embedded in the core was only feasible when long-term heat storage was needed.
Klasifikace
Druh
J<sub>imp</sub> - Článek v periodiku v databázi Web of Science
CEP obor
—
OECD FORD obor
20101 - Civil engineering
Návaznosti výsledku
Projekt
<a href="/cs/project/GA20-00630S" target="_blank" >GA20-00630S: Klimaticky adaptivní prvky integrované ve vývoji energeticky a ekologicky efektivní obálky budovy</a><br>
Návaznosti
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)
Ostatní
Rok uplatnění
2021
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název periodika
Journal of Building Engineering
ISSN
2352-7102
e-ISSN
—
Svazek periodika
36
Číslo periodika v rámci svazku
4
Stát vydavatele periodika
NL - Nizozemsko
Počet stran výsledku
11
Strana od-do
1-11
Kód UT WoS článku
000624447700001
EID výsledku v databázi Scopus
2-s2.0-85098998970