Advanced air distribution technologies for enhanced cleanliness and energy savings in operation rooms
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F00216305%3A26110%2F25%3APU154874" target="_blank" >RIV/00216305:26110/25:PU154874 - isvavai.cz</a>
Výsledek na webu
<a href="https://doi.org/10.18103/mra.v13i1.6079" target="_blank" >https://doi.org/10.18103/mra.v13i1.6079</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.18103/mra.v13i1.6079" target="_blank" >10.18103/mra.v13i1.6079</a>
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Advanced air distribution technologies for enhanced cleanliness and energy savings in operation rooms
Popis výsledku v původním jazyce
This study investigates the impact of advanced airflow distribution technologies on the cleanliness and energy efficiency of operating rooms. A compound laminar airflow ceiling (CLAC) was developed and evaluated using computational fluid dynamics (CFD) simulations, experimental measurements, and field tests. Results show that the CLAC significantly reduces air circulation zones and solid aerosol particle concentrations in critical surgical areas compared to standard laminar airflow ceilings. The findings also reveal that the enhanced air distribution allows for lower airflow rates while maintaining or exceeding cleanliness standards, enabling potential operational cost savings of up to 40 %.
Název v anglickém jazyce
Advanced air distribution technologies for enhanced cleanliness and energy savings in operation rooms
Popis výsledku anglicky
This study investigates the impact of advanced airflow distribution technologies on the cleanliness and energy efficiency of operating rooms. A compound laminar airflow ceiling (CLAC) was developed and evaluated using computational fluid dynamics (CFD) simulations, experimental measurements, and field tests. Results show that the CLAC significantly reduces air circulation zones and solid aerosol particle concentrations in critical surgical areas compared to standard laminar airflow ceilings. The findings also reveal that the enhanced air distribution allows for lower airflow rates while maintaining or exceeding cleanliness standards, enabling potential operational cost savings of up to 40 %.
Klasifikace
Druh
J<sub>ost</sub> - Ostatní články v recenzovaných periodicích
CEP obor
—
OECD FORD obor
30502 - Other medical science
Návaznosti výsledku
Projekt
—
Návaznosti
S - Specificky vyzkum na vysokych skolach
Ostatní
Rok uplatnění
2025
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název periodika
Medical Research Archives
ISSN
2375-1924
e-ISSN
—
Svazek periodika
13
Číslo periodika v rámci svazku
1
Stát vydavatele periodika
US - Spojené státy americké
Počet stran výsledku
18