Influence of the lime slurry droplet spectrum on the efficiency of semi-dry flue gas desulfurization
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F00216305%3A26210%2F13%3APU102106" target="_blank" >RIV/00216305:26210/13:PU102106 - isvavai.cz</a>
Výsledek na webu
—
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Influence of the lime slurry droplet spectrum on the efficiency of semi-dry flue gas desulfurization
Popis výsledku v původním jazyce
A numerical model based on computational fluid dynamics is presented to predict the efficiency of a semi-dry flue gas desulfurization process. The Euler-Lagrange particle tracking method is used to predict both evaporation and mass transfer between the flue gas and the lime slurry droplets. The overall desulfurization process is split into two periods, i.e. the constant-rate and the falling-rate period, during which the fundamental chemical reaction between sulfur dioxide and calcium hydroxide is modeled. The absorption efficiency is calculated for different spray characteristics, taking into account different size spectra of the lime slurry droplets characterized by different standard deviations for a constant mass mean diameter d50 of 25. The resultsare compared with published experiments and show excellent agreement as well as a significant role of the spray characteristics in the FGD efficiency.
Název v anglickém jazyce
Influence of the lime slurry droplet spectrum on the efficiency of semi-dry flue gas desulfurization
Popis výsledku anglicky
A numerical model based on computational fluid dynamics is presented to predict the efficiency of a semi-dry flue gas desulfurization process. The Euler-Lagrange particle tracking method is used to predict both evaporation and mass transfer between the flue gas and the lime slurry droplets. The overall desulfurization process is split into two periods, i.e. the constant-rate and the falling-rate period, during which the fundamental chemical reaction between sulfur dioxide and calcium hydroxide is modeled. The absorption efficiency is calculated for different spray characteristics, taking into account different size spectra of the lime slurry droplets characterized by different standard deviations for a constant mass mean diameter d50 of 25. The resultsare compared with published experiments and show excellent agreement as well as a significant role of the spray characteristics in the FGD efficiency.
Klasifikace
Druh
J<sub>x</sub> - Nezařazeno - Článek v odborném periodiku (Jimp, Jsc a Jost)
CEP obor
JE - Nejaderná energetika, spotřeba a užití energie
OECD FORD obor
—
Návaznosti výsledku
Projekt
<a href="/cs/project/ED0002%2F01%2F01" target="_blank" >ED0002/01/01: NETME Centre (Nové technologie pro strojírenství)</a><br>
Návaznosti
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)
Ostatní
Rok uplatnění
2013
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název periodika
CHEMICAL ENGINEERING & TECHNOLOGY
ISSN
0930-7516
e-ISSN
—
Svazek periodika
36
Číslo periodika v rámci svazku
1
Stát vydavatele periodika
DE - Spolková republika Německo
Počet stran výsledku
11
Strana od-do
156-166
Kód UT WoS článku
000315409200019
EID výsledku v databázi Scopus
—