PLASTIC HEAT EXCHANGER USING TWISTED HOLLOW FIBERS
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F00216305%3A26210%2F14%3APU109258" target="_blank" >RIV/00216305:26210/14:PU109258 - isvavai.cz</a>
Výsledek na webu
—
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
PLASTIC HEAT EXCHANGER USING TWISTED HOLLOW FIBERS
Popis výsledku v původním jazyce
Metallic heat exchangers have a number of well-known disadvantages, such as heavy weight and cost and low resistance to corrosion. Polymeric hollow fiber heat exchangers were proposed about a decade ago as an alternative for low temperature applications.A large-scale heat exchanger was prepared using hollow fibers with a special shape. The heat exchanger's thermal performance was studied using hot ethyleneglycol-water brine flowing inside of the fibers and cool air flowing across the fibers. Experiments showed that the heat exchanger can achieve a significant heat transfer rate and have high values of overall heat-transfer coefficients (60-230 Wm-2K-1). Moreover, obtained results showed that the classical theory is not suitable to estimate outer convection and that special approach should be used.
Název v anglickém jazyce
PLASTIC HEAT EXCHANGER USING TWISTED HOLLOW FIBERS
Popis výsledku anglicky
Metallic heat exchangers have a number of well-known disadvantages, such as heavy weight and cost and low resistance to corrosion. Polymeric hollow fiber heat exchangers were proposed about a decade ago as an alternative for low temperature applications.A large-scale heat exchanger was prepared using hollow fibers with a special shape. The heat exchanger's thermal performance was studied using hot ethyleneglycol-water brine flowing inside of the fibers and cool air flowing across the fibers. Experiments showed that the heat exchanger can achieve a significant heat transfer rate and have high values of overall heat-transfer coefficients (60-230 Wm-2K-1). Moreover, obtained results showed that the classical theory is not suitable to estimate outer convection and that special approach should be used.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
JR - Ostatní strojírenství
OECD FORD obor
—
Návaznosti výsledku
Projekt
<a href="/cs/project/ED0002%2F01%2F01" target="_blank" >ED0002/01/01: NETME Centre (Nové technologie pro strojírenství)</a><br>
Návaznosti
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)
Ostatní
Rok uplatnění
2014
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
Engineering Mechanics 2014, 20th International Conference, May 12-15, 2014, Svratka, Czech Republic
ISBN
978-80-214-4871-1
ISSN
1805-8248
e-ISSN
—
Počet stran výsledku
4
Strana od-do
56-60
Název nakladatele
Institute of Solid Mechanics, Mechatronics and Biomechanics, Faculty of Mechanical Engineering, Brno University of Technology
Místo vydání
Brno
Místo konání akce
Svratka
Datum konání akce
12. 5. 2014
Typ akce podle státní příslušnosti
EUR - Evropská akce
Kód UT WoS článku
000364573900007