The influence of plate corrugations geometry scale factor on performance of plate heat exchanger as condenser of vapour from its mixture with noncondensing gas
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F00216305%3A26210%2F20%3APU137680" target="_blank" >RIV/00216305:26210/20:PU137680 - isvavai.cz</a>
Výsledek na webu
<a href="https://www.sciencedirect.com/science/article/pii/S0360544220307684?via%3Dihub" target="_blank" >https://www.sciencedirect.com/science/article/pii/S0360544220307684?via%3Dihub</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.1016/j.energy.2020.117661" target="_blank" >10.1016/j.energy.2020.117661</a>
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
The influence of plate corrugations geometry scale factor on performance of plate heat exchanger as condenser of vapour from its mixture with noncondensing gas
Popis výsledku v původním jazyce
The condensation of steam from a steam-air mixture is studied experimentally at three samples of Plate Heat Exchanger (PHE) channel. For three test samples corrugations are similar but differ in scale with the height 5, 7.5 and 10 mm. The results of tests are compared to calculations with one dimensional mathematical model of the process. The identification of correlations for local heat and mass transfer coefficients, as also friction factor in condensing two-phase flow, is made by comparison of computed results with tests data. The correlations for condensing two-phase flow are based on single-phase correlations for considered channels. For mass transfer coefficients, the best results are obtained using a stagnant film model for accounting transverse mass flux influence. For the prediction of pressure losses in two-phase condensing flow, the correlation with Lockhart-Martinelli parameters is used for zones of low liquid flow rates. For other channelzones are proposed its combination with an equation based on a dispersed annular model of flow structure. The presented equations can be used for calculation of heat and mass transfer intensity and pressure losses in two-phase condensing flow when designing PHE for condensation of steam from its mixture with air by local process parameters.
Název v anglickém jazyce
The influence of plate corrugations geometry scale factor on performance of plate heat exchanger as condenser of vapour from its mixture with noncondensing gas
Popis výsledku anglicky
The condensation of steam from a steam-air mixture is studied experimentally at three samples of Plate Heat Exchanger (PHE) channel. For three test samples corrugations are similar but differ in scale with the height 5, 7.5 and 10 mm. The results of tests are compared to calculations with one dimensional mathematical model of the process. The identification of correlations for local heat and mass transfer coefficients, as also friction factor in condensing two-phase flow, is made by comparison of computed results with tests data. The correlations for condensing two-phase flow are based on single-phase correlations for considered channels. For mass transfer coefficients, the best results are obtained using a stagnant film model for accounting transverse mass flux influence. For the prediction of pressure losses in two-phase condensing flow, the correlation with Lockhart-Martinelli parameters is used for zones of low liquid flow rates. For other channelzones are proposed its combination with an equation based on a dispersed annular model of flow structure. The presented equations can be used for calculation of heat and mass transfer intensity and pressure losses in two-phase condensing flow when designing PHE for condensation of steam from its mixture with air by local process parameters.
Klasifikace
Druh
J<sub>imp</sub> - Článek v periodiku v databázi Web of Science
CEP obor
—
OECD FORD obor
20704 - Energy and fuels
Návaznosti výsledku
Projekt
<a href="/cs/project/EF15_003%2F0000456" target="_blank" >EF15_003/0000456: Laboratoř integrace procesů pro trvalou udržitelnost</a><br>
Návaznosti
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)
Ostatní
Rok uplatnění
2020
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název periodika
Energy
ISSN
0360-5442
e-ISSN
1873-6785
Svazek periodika
neuveden
Číslo periodika v rámci svazku
201
Stát vydavatele periodika
GB - Spojené království Velké Británie a Severního Irska
Počet stran výsledku
11
Strana od-do
117661-117661
Kód UT WoS článku
000534685400078
EID výsledku v databázi Scopus
2-s2.0-85083651712