Cable Thermal Model in Protection System
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F00216305%3A26220%2F08%3APU77077" target="_blank" >RIV/00216305:26220/08:PU77077 - isvavai.cz</a>
Výsledek na webu
—
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Cable Thermal Model in Protection System
Popis výsledku v původním jazyce
Certain sophisticated digital relays offer the possibility of protecting cables by means of a thermal model with pa-rameter setting using the knowledge of the cable heating time constant and given operating conditions. The principle of the thermal modelis based on the theory of heating up a conductor by the flowing current and therefore it is neces-sary to know to what extent the theory is respected by the relay and what consequences its application brings. The paper presents a comparison between the simulation of heating a real cable by means of a mathematical model and the algorithm for analyzing the cable temperature used in digital relays. It also deals with the definition of the thermal model breaking characteristic as a parametric function of the cable rated current capable of selective setting of the relay and its coordination with the protective system.
Název v anglickém jazyce
Cable Thermal Model in Protection System
Popis výsledku anglicky
Certain sophisticated digital relays offer the possibility of protecting cables by means of a thermal model with pa-rameter setting using the knowledge of the cable heating time constant and given operating conditions. The principle of the thermal modelis based on the theory of heating up a conductor by the flowing current and therefore it is neces-sary to know to what extent the theory is respected by the relay and what consequences its application brings. The paper presents a comparison between the simulation of heating a real cable by means of a mathematical model and the algorithm for analyzing the cable temperature used in digital relays. It also deals with the definition of the thermal model breaking characteristic as a parametric function of the cable rated current capable of selective setting of the relay and its coordination with the protective system.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
JE - Nejaderná energetika, spotřeba a užití energie
OECD FORD obor
—
Návaznosti výsledku
Projekt
—
Návaznosti
Z - Vyzkumny zamer (s odkazem do CEZ)
Ostatní
Rok uplatnění
2008
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
Proceedings of 9th International Scientific Conference Electric Power Engineering 2008
ISBN
978-80-214-3650-3
ISSN
—
e-ISSN
—
Počet stran výsledku
4
Strana od-do
—
Název nakladatele
Neuveden
Místo vydání
Neuveden
Místo konání akce
Hotel Santon, Brno
Datum konání akce
13. 5. 2008
Typ akce podle státní příslušnosti
EUR - Evropská akce
Kód UT WoS článku
000263964600035