SIMULATION AND VERIFICATION OF METHODS FOR PAR-TIAL DISCHARGE SOURCE LOCALIZATION
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F00216305%3A26220%2F12%3APU98253" target="_blank" >RIV/00216305:26220/12:PU98253 - isvavai.cz</a>
Výsledek na webu
—
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
čeština
Název v původním jazyce
SIMULATION AND VERIFICATION OF METHODS FOR PAR-TIAL DISCHARGE SOURCE LOCALIZATION
Popis výsledku v původním jazyce
This article deals with possibilities of localization of partial discharges (PD) in oil power transformers. Localization can be performed by means of analysis of UHF waveforms which are measured during activity of the partial discharges. The time differences of arrival (TDOA) of the waveforms related to transient process occurrence in the signals are the main input parameters for localization methods. In order to estimate the position of the signal source in 3D space a minimum of four antennas has to beused, since the time of the PD occurrence is unknown. For localization purposes the system of nonlinear equations has to be solved. This can be performed by means of analytical or numerical methods. Both of the methods have their own advantages and disadvantages. The application of both approaches for signal source localization in measurement model will be presented in this paper. The methods will be compared in view of their suitability for a given configuration of antenna system
Název v anglickém jazyce
SIMULATION AND VERIFICATION OF METHODS FOR PAR-TIAL DISCHARGE SOURCE LOCALIZATION
Popis výsledku anglicky
This article deals with possibilities of localization of partial discharges (PD) in oil power transformers. Localization can be performed by means of analysis of UHF waveforms which are measured during activity of the partial discharges. The time differences of arrival (TDOA) of the waveforms related to transient process occurrence in the signals are the main input parameters for localization methods. In order to estimate the position of the signal source in 3D space a minimum of four antennas has to beused, since the time of the PD occurrence is unknown. For localization purposes the system of nonlinear equations has to be solved. This can be performed by means of analytical or numerical methods. Both of the methods have their own advantages and disadvantages. The application of both approaches for signal source localization in measurement model will be presented in this paper. The methods will be compared in view of their suitability for a given configuration of antenna system
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
JA - Elektronika a optoelektronika, elektrotechnika
OECD FORD obor
—
Návaznosti výsledku
Projekt
<a href="/cs/project/FR-TI1%2F001" target="_blank" >FR-TI1/001: Výzkum a vývoj detekce výbojové aktivity ve výkonových olejových transformátorech</a><br>
Návaznosti
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)
Ostatní
Rok uplatnění
2012
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
Proceedings of the 18th Conference Student EEICT 2012
ISBN
978-80-214-4462-1
ISSN
—
e-ISSN
—
Počet stran výsledku
5
Strana od-do
273-277
Název nakladatele
LITERA Brno
Místo vydání
Brno, ČR
Místo konání akce
Brno
Datum konání akce
26. 4. 2012
Typ akce podle státní příslušnosti
CST - Celostátní akce
Kód UT WoS článku
—