Diagnosis of heat loss in the molded case circuit breaker contacts in nominal current
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F00216305%3A26220%2F12%3APU98388" target="_blank" >RIV/00216305:26220/12:PU98388 - isvavai.cz</a>
Výsledek na webu
—
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Diagnosis of heat loss in the molded case circuit breaker contacts in nominal current
Popis výsledku v původním jazyce
The paper deals with an analysis of temperature on the rotary breaking system of a molded case circuit breaker. Molded case circuit breaker has a modern breaking me-chanism with uses rotary breaking system. The main makes contact move along circular path. The current path is interrupted in two places where some thermal losses rise in running order. The size of the thermal losses depends on the transient resistance. System of springs is used for eliminating the transient resistance between contacts. Theright setting force of these springs is important for right function of the thermal release. In the opposite case the nominal current can be incorrectly evaluated and the circuit breaker turn off at the wrong time. Thermal losses are computed using finite element method (FEM). The first part of the paper focuses on the calculation of the thermal losses of the current path in nominal current 630 A. The contact force changes from 20 to 100 N. The second part of the paper focuses on laborat
Název v anglickém jazyce
Diagnosis of heat loss in the molded case circuit breaker contacts in nominal current
Popis výsledku anglicky
The paper deals with an analysis of temperature on the rotary breaking system of a molded case circuit breaker. Molded case circuit breaker has a modern breaking me-chanism with uses rotary breaking system. The main makes contact move along circular path. The current path is interrupted in two places where some thermal losses rise in running order. The size of the thermal losses depends on the transient resistance. System of springs is used for eliminating the transient resistance between contacts. Theright setting force of these springs is important for right function of the thermal release. In the opposite case the nominal current can be incorrectly evaluated and the circuit breaker turn off at the wrong time. Thermal losses are computed using finite element method (FEM). The first part of the paper focuses on the calculation of the thermal losses of the current path in nominal current 630 A. The contact force changes from 20 to 100 N. The second part of the paper focuses on laborat
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
JE - Nejaderná energetika, spotřeba a užití energie
OECD FORD obor
—
Návaznosti výsledku
Projekt
<a href="/cs/project/ED0014%2F01%2F01" target="_blank" >ED0014/01/01: Centrum výzkumu a využití obnovitelných zdrojů energie</a><br>
Návaznosti
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)<br>S - Specificky vyzkum na vysokych skolach
Ostatní
Rok uplatnění
2012
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
Proceedings of the 13th International Scientific Conference Electric Power Engineering 2012
ISBN
978-80-214-4514-7
ISSN
—
e-ISSN
—
Počet stran výsledku
5
Strana od-do
911-915
Název nakladatele
Brno University of Technology
Místo vydání
Brno
Místo konání akce
Brno
Datum konání akce
23. 5. 2012
Typ akce podle státní příslušnosti
EUR - Evropská akce
Kód UT WoS článku
—