The Influence of Ripple Control Signal on Protection Relay Operation
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F00216305%3A26220%2F19%3APU133387" target="_blank" >RIV/00216305:26220/19:PU133387 - isvavai.cz</a>
Výsledek na webu
<a href="https://eesymp.fei.tuke.sk/viewabstract.php?id=182" target="_blank" >https://eesymp.fei.tuke.sk/viewabstract.php?id=182</a>
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
The Influence of Ripple Control Signal on Protection Relay Operation
Popis výsledku v původním jazyce
A ripple control system is a form of load management used in many countries. It enables to remotely control devices using a high-frequency signal (usually between 100 – 1600 Hz) superimposed onto the fundamental frequency of the power system. Since the distance protection evaluates the fault distance using the fundamental voltages and currents, an error can occur if the analyzed signal contains a higher level of inter-harmonics. This paper describes the impact of inter-harmonic distortion on the fault location. The power system network is modeled utilizing the PSCAD software and the simulation outputs are used to test the distance protection. In the model, the ripple control source with frequencies of 183.3 Hz and 216.6 Hz is used. The performed tests show that the distance protection ability to locate the fault is not significantly influenced by the ripple control signal.
Název v anglickém jazyce
The Influence of Ripple Control Signal on Protection Relay Operation
Popis výsledku anglicky
A ripple control system is a form of load management used in many countries. It enables to remotely control devices using a high-frequency signal (usually between 100 – 1600 Hz) superimposed onto the fundamental frequency of the power system. Since the distance protection evaluates the fault distance using the fundamental voltages and currents, an error can occur if the analyzed signal contains a higher level of inter-harmonics. This paper describes the impact of inter-harmonic distortion on the fault location. The power system network is modeled utilizing the PSCAD software and the simulation outputs are used to test the distance protection. In the model, the ripple control source with frequencies of 183.3 Hz and 216.6 Hz is used. The performed tests show that the distance protection ability to locate the fault is not significantly influenced by the ripple control signal.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
—
OECD FORD obor
20201 - Electrical and electronic engineering
Návaznosti výsledku
Projekt
—
Návaznosti
S - Specificky vyzkum na vysokych skolach
Ostatní
Rok uplatnění
2019
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
Proceedings of the 10th International Scientific Symposium on Electrical Power Engineering
ISBN
978-80-553-3324-3
ISSN
—
e-ISSN
—
Počet stran výsledku
4
Strana od-do
464-467
Název nakladatele
Technical University of Kosice
Místo vydání
Stará Lesná
Místo konání akce
Stará Lesná
Datum konání akce
16. 9. 2019
Typ akce podle státní příslušnosti
WRD - Celosvětová akce
Kód UT WoS článku
000531434400091