The paper discusses possible contribution of distributed measurement system installed in a mesh LV network in means of non-standard operation states or faults detection. A numerical model of real, highly interconnected mesh MV/LV network is created and is used for cascading failure simulations. Possibilities of cascading failure indication are examined based on calculating voltages and currents in the network. Distributed voltage monitoring potential is assessed based on limited number of measuring devices, selectively placed in the LV network. Simulations show that the impact of distributed voltage measurement is insignificant. As a result, monitoring of currents at MV/LV transformer stations is proposed and further examined. For both voltage and current monitoring, variants of different monitoring penetration are discussed.
Název v anglickém jazyce
Indication of Abnormal Operation Conditions in a Mesh Network Based on Data from Distributed Measurement
Popis výsledku anglicky
The paper discusses possible contribution of distributed measurement system installed in a mesh LV network in means of non-standard operation states or faults detection. A numerical model of real, highly interconnected mesh MV/LV network is created and is used for cascading failure simulations. Possibilities of cascading failure indication are examined based on calculating voltages and currents in the network. Distributed voltage monitoring potential is assessed based on limited number of measuring devices, selectively placed in the LV network. Simulations show that the impact of distributed voltage measurement is insignificant. As a result, monitoring of currents at MV/LV transformer stations is proposed and further examined. For both voltage and current monitoring, variants of different monitoring penetration are discussed.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
—
OECD FORD obor
20201 - Electrical and electronic engineering
Návaznosti výsledku
Projekt
—
Návaznosti
S - Specificky vyzkum na vysokych skolach
Ostatní
Rok uplatnění
2021
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
CIRED 2021 - The 26th International Conference and Exhibition on Electricity Distribution
ISBN
978-1-83953-591-8
ISSN
2732-4494
e-ISSN
—
Počet stran výsledku
5
Strana od-do
1567-1571
Název nakladatele
Institution of Engineering and Technology
Místo vydání
United Kingdom
Místo konání akce
Online/Virtual, Switzerland
Datum konání akce
20. 9. 2021
Typ akce podle státní příslušnosti
WRD - Celosvětová akce
Kód UT WoS článku
—