Evaluation of corrosion of long-term exposed aluminium conductor
Popis výsledku v původním jazyce
The goal of the study was to assess corrosion of a cable bundle after a forty-year exposure to atmosphere. The assessed bundle consisted of a galvanized steel wire carrying core and aluminium external guide wires. Optical microscopy, electron dispersivemicroscopy and X-ray diffraction techniques were used for the assessment. Aluminium oxide was identifi ed to be the most prevailing aluminium corrosion product. The average residual thickness of the steel wire zinc coat was 33 ?m, even though there werelocations where the zinc coat corroded through totally. Service life of aluminium wires is limited predominantly by the pitting corrosion rate, which reached 5 ?m/year.
Název v anglickém jazyce
Evaluation of corrosion of long-term exposed aluminium conductor
Popis výsledku anglicky
The goal of the study was to assess corrosion of a cable bundle after a forty-year exposure to atmosphere. The assessed bundle consisted of a galvanized steel wire carrying core and aluminium external guide wires. Optical microscopy, electron dispersivemicroscopy and X-ray diffraction techniques were used for the assessment. Aluminium oxide was identifi ed to be the most prevailing aluminium corrosion product. The average residual thickness of the steel wire zinc coat was 33 ?m, even though there werelocations where the zinc coat corroded through totally. Service life of aluminium wires is limited predominantly by the pitting corrosion rate, which reached 5 ?m/year.
Klasifikace
Druh
J<sub>SC</sub> - Článek v periodiku v databázi SCOPUS
CEP obor
—
OECD FORD obor
10405 - Electrochemistry (dry cells, batteries, fuel cells, corrosion metals, electrolysis)
Návaznosti výsledku
Projekt
—
Návaznosti
I - Institucionalni podpora na dlouhodoby koncepcni rozvoj vyzkumne organizace
Ostatní
Rok uplatnění
2013
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název periodika
Koroze a ochrana materiálu
ISSN
1804-1213
e-ISSN
—
Svazek periodika
57
Číslo periodika v rámci svazku
1
Stát vydavatele periodika
CZ - Česká republika
Počet stran výsledku
10
Strana od-do
25-34
Kód UT WoS článku
—
EID výsledku v databázi Scopus
2-s2.0-85010742178