Popis výsledku v původním jazyce
The article describes the corrosion attack and premature damage in stainless steel drinking water piping installed in a hospital. After only two years of service, intensive pitting and crevice corrosion was observed near welded joints, resulting in wall perforation. The analyses made on damaged tubes revealed that corrosion attack started in the root parts of weldments due to welding defects, mainly incomplete root penetration, lack of fusion, and inadequate weld root shielding. Such defects formed narrow crevices in which a restricted exchange of ions and electric charge with the environment caused fast and extensive corrosion damage. The presence of chlorine dioxide, used for water disinfection, also played a significant role in the initiation of corrosion, as chlorine or chloride ions disrupt the protective oxidic film on the metal surface and facilitate the penetration of oxygen.
Název v anglickém jazyce
Corrosion Damage Analysis of Drinking Water Piping
Popis výsledku anglicky
The article describes the corrosion attack and premature damage in stainless steel drinking water piping installed in a hospital. After only two years of service, intensive pitting and crevice corrosion was observed near welded joints, resulting in wall perforation. The analyses made on damaged tubes revealed that corrosion attack started in the root parts of weldments due to welding defects, mainly incomplete root penetration, lack of fusion, and inadequate weld root shielding. Such defects formed narrow crevices in which a restricted exchange of ions and electric charge with the environment caused fast and extensive corrosion damage. The presence of chlorine dioxide, used for water disinfection, also played a significant role in the initiation of corrosion, as chlorine or chloride ions disrupt the protective oxidic film on the metal surface and facilitate the penetration of oxygen.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
—
OECD FORD obor
20501 - Materials engineering
Návaznosti výsledku
Projekt
—
Návaznosti
I - Institucionalni podpora na dlouhodoby koncepcni rozvoj vyzkumne organizace
Ostatní
Rok uplatnění
2025
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
METAL 2025 CONFERENCE PROCEEDINGS
ISBN
978-80-88365-27-3
ISSN
2694-9296
e-ISSN
—
Počet stran výsledku
6
Strana od-do
230-235
Název nakladatele
TANGER Ltd.
Místo vydání
Ostrava
Místo konání akce
Brno
Datum konání akce
21. 5. 2025
Typ akce podle státní příslušnosti
WRD - Celosvětová akce
Kód UT WoS článku
—