Elimination of three-phase transformer inrush current through core forced magnetization and simultaneous closing
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F46747885%3A24220%2F10%3A%230001720" target="_blank" >RIV/46747885:24220/10:#0001720 - isvavai.cz</a>
Výsledek na webu
—
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Elimination of three-phase transformer inrush current through core forced magnetization and simultaneous closing
Popis výsledku v původním jazyce
The inrush current occurs during transformer energization due to flux saturation in the core. Controlled switching connects transformer to power grid in proper phase angle derived from core remanent fluxes. The DC forced magnetization prior to transformer energization is one of simultaneous closing strategy methods. Active intervention to the transformer remanent flux was realized as a DC power supply with current splitter and automated disconnection circuit. Inrush currents were measured in dependencyon switch on angle. Resulting current maps determine the range of switch on angles in which the current does not exceed the limits. This angle range restricts the choice of synchronous switch closing time scatter. This paper shows the results of a research on possible closing time scatter dependency both on forced pre-magnetizing current and on transformer working flux for star, grounded star and delta winding connections.
Název v anglickém jazyce
Elimination of three-phase transformer inrush current through core forced magnetization and simultaneous closing
Popis výsledku anglicky
The inrush current occurs during transformer energization due to flux saturation in the core. Controlled switching connects transformer to power grid in proper phase angle derived from core remanent fluxes. The DC forced magnetization prior to transformer energization is one of simultaneous closing strategy methods. Active intervention to the transformer remanent flux was realized as a DC power supply with current splitter and automated disconnection circuit. Inrush currents were measured in dependencyon switch on angle. Resulting current maps determine the range of switch on angles in which the current does not exceed the limits. This angle range restricts the choice of synchronous switch closing time scatter. This paper shows the results of a research on possible closing time scatter dependency both on forced pre-magnetizing current and on transformer working flux for star, grounded star and delta winding connections.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
JA - Elektronika a optoelektronika, elektrotechnika
OECD FORD obor
—
Návaznosti výsledku
Projekt
<a href="/cs/project/GP102%2F08%2FP453" target="_blank" >GP102/08/P453: Omezování zapínacího proudu transformátorů</a><br>
Návaznosti
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)
Ostatní
Rok uplatnění
2010
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
Applied Electronics
ISBN
978-80-7043-865-7
ISSN
1803-7232
e-ISSN
—
Počet stran výsledku
4
Strana od-do
—
Název nakladatele
University of West Bohemia
Místo vydání
Pilsen
Místo konání akce
Pilsen
Datum konání akce
1. 1. 2010
Typ akce podle státní příslušnosti
WRD - Celosvětová akce
Kód UT WoS článku
—