Changes in electrical insulation properties of fire resistant cables during a fire incident
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F49777513%3A23220%2F13%3A43918746" target="_blank" >RIV/49777513:23220/13:43918746 - isvavai.cz</a>
Výsledek na webu
<a href="http://ieeexplore.ieee.org/xpl/articleDetails.jsp?arnumber=6619775" target="_blank" >http://ieeexplore.ieee.org/xpl/articleDetails.jsp?arnumber=6619775</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.1109/ICSD.2013.6619775" target="_blank" >10.1109/ICSD.2013.6619775</a>
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Changes in electrical insulation properties of fire resistant cables during a fire incident
Popis výsledku v původním jazyce
This paper is focused on the comparison of the behavior of two low fire hazard cables of different construction under fire conditions. The fire barrier of the first one was created by glass and glass mica tape while the second one was protected by ceramifible silicone insulation. The insulation resistance between insulated cores of cables was measured and periodically recorded. The fire test was done according to IEC 60331, the whole test took 90 minutes of a burning and 15 minutes of cooling. The results show interesting changes in insulation properties of the cable in the first few minutes when the insulation resistance decreases by several orders of magnitude. On the other hand, during cooling the insulation, the state of cables is almost restored to its initial values.
Název v anglickém jazyce
Changes in electrical insulation properties of fire resistant cables during a fire incident
Popis výsledku anglicky
This paper is focused on the comparison of the behavior of two low fire hazard cables of different construction under fire conditions. The fire barrier of the first one was created by glass and glass mica tape while the second one was protected by ceramifible silicone insulation. The insulation resistance between insulated cores of cables was measured and periodically recorded. The fire test was done according to IEC 60331, the whole test took 90 minutes of a burning and 15 minutes of cooling. The results show interesting changes in insulation properties of the cable in the first few minutes when the insulation resistance decreases by several orders of magnitude. On the other hand, during cooling the insulation, the state of cables is almost restored to its initial values.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
JA - Elektronika a optoelektronika, elektrotechnika
OECD FORD obor
—
Návaznosti výsledku
Projekt
<a href="/cs/project/ED2.1.00%2F03.0094" target="_blank" >ED2.1.00/03.0094: Regionální inovační centrum elektrotechniky (RICE)</a><br>
Návaznosti
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)
Ostatní
Rok uplatnění
2013
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
11th International Conference on Solid Dielectrics (ICSD)
ISBN
978-1-4799-0807-3
ISSN
1553-5282
e-ISSN
—
Počet stran výsledku
4
Strana od-do
670-673
Název nakladatele
The Institute of Electrical and Electronics Engineers, Inc.
Místo vydání
Piscataway
Místo konání akce
Bologna
Datum konání akce
30. 6. 2013
Typ akce podle státní příslušnosti
WRD - Celosvětová akce
Kód UT WoS článku
—