Analysis of the inductive effects of overhead lines to close pipelines
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F49777513%3A23220%2F14%3A43924098" target="_blank" >RIV/49777513:23220/14:43924098 - isvavai.cz</a>
Výsledek na webu
—
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Analysis of the inductive effects of overhead lines to close pipelines
Popis výsledku v původním jazyce
This paper deals with the calculation of dangerous inductive effects of overhead very high voltage lines on close steel pipelines, with a focus on refining the input data precision. The problem of evaluating mutual electromagnetic influence very high voltage overhead lines and nearby pipeline systems has high importance not only for the lifetime and operating conditions of both devices, but especially for safety. This paper is about special aspects of this problem. Attention will be paid to a substantial element needed to calculate longitudinal voltage, which is the complete reduction factor, which represents the degree of influence limitation of magnetic field on the affected in earth stored facilities and is dependent not just only on the overhead earth wire and close railway yards, but also on all other parallel in earth deposited metal structures. Commonly used pipeline protection from the effects of the inductive of HV overhead lines is installing parallel of grounding FeZn strap
Název v anglickém jazyce
Analysis of the inductive effects of overhead lines to close pipelines
Popis výsledku anglicky
This paper deals with the calculation of dangerous inductive effects of overhead very high voltage lines on close steel pipelines, with a focus on refining the input data precision. The problem of evaluating mutual electromagnetic influence very high voltage overhead lines and nearby pipeline systems has high importance not only for the lifetime and operating conditions of both devices, but especially for safety. This paper is about special aspects of this problem. Attention will be paid to a substantial element needed to calculate longitudinal voltage, which is the complete reduction factor, which represents the degree of influence limitation of magnetic field on the affected in earth stored facilities and is dependent not just only on the overhead earth wire and close railway yards, but also on all other parallel in earth deposited metal structures. Commonly used pipeline protection from the effects of the inductive of HV overhead lines is installing parallel of grounding FeZn strap
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
JE - Nejaderná energetika, spotřeba a užití energie
OECD FORD obor
—
Návaznosti výsledku
Projekt
—
Návaznosti
S - Specificky vyzkum na vysokych skolach
Ostatní
Rok uplatnění
2014
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
Proceedings of the 2014 15th International Scientific Conference on Electric Power Engineering
ISBN
978-1-4799-3806-3
ISSN
—
e-ISSN
—
Počet stran výsledku
6
Strana od-do
495-500
Název nakladatele
Brno University of Technology
Místo vydání
Brno
Místo konání akce
Hotel Santon,Brno
Datum konání akce
12. 5. 2014
Typ akce podle státní příslušnosti
WRD - Celosvětová akce
Kód UT WoS článku
—