Utilization of events measured by WAMS-BIOZE-detector for system voltage stability evaluation
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F49777513%3A23220%2F16%3A43930271" target="_blank" >RIV/49777513:23220/16:43930271 - isvavai.cz</a>
Výsledek na webu
<a href="http://www.sciencedirect.com/science/article/pii/S2405896316323667" target="_blank" >http://www.sciencedirect.com/science/article/pii/S2405896316323667</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.1016/j.ifacol.2016.10.747" target="_blank" >10.1016/j.ifacol.2016.10.747</a>
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Utilization of events measured by WAMS-BIOZE-detector for system voltage stability evaluation
Popis výsledku v původním jazyce
The paper summarizes results of research work focused on development of the voltage stability assessment method and its software implementation. Developed voltage stability detection algorithm is based on local synchronous phasor measurement. The Thevenin equivalence based assessment method, the identification algorithm as well as the developed WAMS-BIOZE-Detektor software are presented. The proposed voltage stability indices have different sensitivity to events in power systems. Sensitivity of the indices was tested by using records of various disturbances and failures in a HV grid. Test results validate applicability of the indices in practice. Finally, the index with the highest applicability for online detection is recommended.
Název v anglickém jazyce
Utilization of events measured by WAMS-BIOZE-detector for system voltage stability evaluation
Popis výsledku anglicky
The paper summarizes results of research work focused on development of the voltage stability assessment method and its software implementation. Developed voltage stability detection algorithm is based on local synchronous phasor measurement. The Thevenin equivalence based assessment method, the identification algorithm as well as the developed WAMS-BIOZE-Detektor software are presented. The proposed voltage stability indices have different sensitivity to events in power systems. Sensitivity of the indices was tested by using records of various disturbances and failures in a HV grid. Test results validate applicability of the indices in practice. Finally, the index with the highest applicability for online detection is recommended.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
JA - Elektronika a optoelektronika, elektrotechnika
OECD FORD obor
—
Návaznosti výsledku
Projekt
—
Návaznosti
S - Specificky vyzkum na vysokych skolach
Ostatní
Rok uplatnění
2016
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
IFAC-PapersOnline
ISBN
—
ISSN
2405-8963
e-ISSN
—
Počet stran výsledku
6
Strana od-do
364-369
Název nakladatele
Elsevier
Místo vydání
Amsterdam
Místo konání akce
Prague, Czech Republic
Datum konání akce
11. 10. 2016
Typ akce podle státní příslušnosti
WRD - Celosvětová akce
Kód UT WoS článku
—