Origin of the circulating currents on the quadrupple EHV/VHV transmission line during the specific operation
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F49777513%3A23220%2F17%3A43931858" target="_blank" >RIV/49777513:23220/17:43931858 - isvavai.cz</a>
Výsledek na webu
<a href="http://ieeexplore.ieee.org/document/7967235/" target="_blank" >http://ieeexplore.ieee.org/document/7967235/</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.1109/EPE.2017.7967235" target="_blank" >10.1109/EPE.2017.7967235</a>
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Origin of the circulating currents on the quadrupple EHV/VHV transmission line during the specific operation
Popis výsledku v původním jazyce
This paper is focused on an analysis of mutual influence between the circuits of different voltage level located on the same pylon. The significant consequence of these mutual couplings between all conductors including earth wires is a voltage induced into conductors which results in current asymmetry not only during a specific operations but also during standard operations. In the case, that some circuits are switchedoff, the switched-on circuits induce voltage via inductive couplings to the switched-off circuits, which brings some problems for instance the circulating currents in the unloaded line. This phenomenon has been analysed on the quadruple EHV/VHV non-transposed transmission line and the capacitive couplings were neglected.
Název v anglickém jazyce
Origin of the circulating currents on the quadrupple EHV/VHV transmission line during the specific operation
Popis výsledku anglicky
This paper is focused on an analysis of mutual influence between the circuits of different voltage level located on the same pylon. The significant consequence of these mutual couplings between all conductors including earth wires is a voltage induced into conductors which results in current asymmetry not only during a specific operations but also during standard operations. In the case, that some circuits are switchedoff, the switched-on circuits induce voltage via inductive couplings to the switched-off circuits, which brings some problems for instance the circulating currents in the unloaded line. This phenomenon has been analysed on the quadruple EHV/VHV non-transposed transmission line and the capacitive couplings were neglected.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
—
OECD FORD obor
20201 - Electrical and electronic engineering
Návaznosti výsledku
Projekt
—
Návaznosti
S - Specificky vyzkum na vysokych skolach
Ostatní
Rok uplatnění
2017
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
Proceedings of the 2017 18th International Scientific Conference on Electric Power Engineering (EPE)
ISBN
978-1-5090-6405-2
ISSN
—
e-ISSN
neuvedeno
Počet stran výsledku
5
Strana od-do
13-17
Název nakladatele
IEEE
Místo vydání
Piscataway
Místo konání akce
Kouty nad Desnou, Czech Republic
Datum konání akce
17. 5. 2017
Typ akce podle státní příslušnosti
WRD - Celosvětová akce
Kód UT WoS článku
—