Transient analysis of multi-circuit overhead transmission lines with two voltage levels
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F49777513%3A23220%2F17%3A43932378" target="_blank" >RIV/49777513:23220/17:43932378 - isvavai.cz</a>
Výsledek na webu
—
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Transient analysis of multi-circuit overhead transmission lines with two voltage levels
Popis výsledku v původním jazyce
In this paper a method for a common transient analysis for the multi-circuit overhead transmission line is presented. It takes into account the influences of the mutual couplings between the conductors. It is based on two-port approach, where the phase conductors and earth wires are modelled by inductive and capacitive coupled cascades of twoports. For a considered network model, a system of ordinary differential equations (ODE) has been formulated and it has been solved in MATLAB using Runge-Kutta method of 4th order. It results in the time distribution of currents and voltages in all conductors. In this paper a system with four threephase system of two voltage levels (EHV and HV) has been analysed. The calculations were performed for the typical transients that can occur on EHV/HV line - the single phase short circuit together with automatic reclose cycle.
Název v anglickém jazyce
Transient analysis of multi-circuit overhead transmission lines with two voltage levels
Popis výsledku anglicky
In this paper a method for a common transient analysis for the multi-circuit overhead transmission line is presented. It takes into account the influences of the mutual couplings between the conductors. It is based on two-port approach, where the phase conductors and earth wires are modelled by inductive and capacitive coupled cascades of twoports. For a considered network model, a system of ordinary differential equations (ODE) has been formulated and it has been solved in MATLAB using Runge-Kutta method of 4th order. It results in the time distribution of currents and voltages in all conductors. In this paper a system with four threephase system of two voltage levels (EHV and HV) has been analysed. The calculations were performed for the typical transients that can occur on EHV/HV line - the single phase short circuit together with automatic reclose cycle.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
—
OECD FORD obor
20201 - Electrical and electronic engineering
Návaznosti výsledku
Projekt
—
Návaznosti
S - Specificky vyzkum na vysokych skolach
Ostatní
Rok uplatnění
2017
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
Proceedings of the 9th International Scientific Symposium on Electrical Power Engineering (ELEKTROENERGETIKA 2017)
ISBN
978-80-553-3195-9
ISSN
—
e-ISSN
neuvedeno
Počet stran výsledku
6
Strana od-do
596-601
Název nakladatele
Technical University of Košice
Místo vydání
Košice
Místo konání akce
Stará Lesná, Slovenská republika
Datum konání akce
12. 9. 2017
Typ akce podle státní příslušnosti
WRD - Celosvětová akce