Sliding DFT based grid to ground admittance estimation with guaranteed numerical stability
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F49777513%3A23220%2F17%3A43932838" target="_blank" >RIV/49777513:23220/17:43932838 - isvavai.cz</a>
Výsledek na webu
<a href="http://ieeexplore.ieee.org/document/8216747/" target="_blank" >http://ieeexplore.ieee.org/document/8216747/</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.1109/IECON.2017.8216747" target="_blank" >10.1109/IECON.2017.8216747</a>
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Sliding DFT based grid to ground admittance estimation with guaranteed numerical stability
Popis výsledku v původním jazyce
This paper describes the sliding discrete Fourier transform algorithm (SDFT) for parallel admittance estimation. The SDFT is a popular algorithm for continual single-point or several-point spectral analyzes of discrete time signals. The main drawback of the SDFT is a numerical stability issue. The paper describes the algorithm of SDFT with guaranteed numerical stability by parallel spectra computation. Furthermore, the paper presents the application of SDFT for continual parameter identification of grid to ground admittance of ac power distribution network. The grid admittance is analyzed by voltage response on injected current into auxiliary winding of the Petersen coil. The spectral analyses of injected current and voltage response are used for Petersen coil tuning. The current is injected by Hbridge voltage source inverter.
Název v anglickém jazyce
Sliding DFT based grid to ground admittance estimation with guaranteed numerical stability
Popis výsledku anglicky
This paper describes the sliding discrete Fourier transform algorithm (SDFT) for parallel admittance estimation. The SDFT is a popular algorithm for continual single-point or several-point spectral analyzes of discrete time signals. The main drawback of the SDFT is a numerical stability issue. The paper describes the algorithm of SDFT with guaranteed numerical stability by parallel spectra computation. Furthermore, the paper presents the application of SDFT for continual parameter identification of grid to ground admittance of ac power distribution network. The grid admittance is analyzed by voltage response on injected current into auxiliary winding of the Petersen coil. The spectral analyses of injected current and voltage response are used for Petersen coil tuning. The current is injected by Hbridge voltage source inverter.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
—
OECD FORD obor
20201 - Electrical and electronic engineering
Návaznosti výsledku
Projekt
<a href="/cs/project/LO1607" target="_blank" >LO1607: RICE – Nové technologie a koncepce pro inteligentní průmyslové systémy</a><br>
Návaznosti
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)
Ostatní
Rok uplatnění
2017
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
Proceedings of the IECON 2017 : 43rd Annual Conference of the IEEE Industrial Electronics Society
ISBN
978-1-5386-1127-2
ISSN
—
e-ISSN
neuvedeno
Počet stran výsledku
6
Strana od-do
4344-4349
Název nakladatele
IEEE
Místo vydání
Piscataway
Místo konání akce
Beijing, China
Datum konání akce
29. 10. 2017
Typ akce podle státní příslušnosti
WRD - Celosvětová akce
Kód UT WoS článku
—