Influence of Load Impedance on PD Monitoring Sensitivity for High-Voltage Cable Lines
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F49777513%3A23220%2F25%3A43976490" target="_blank" >RIV/49777513:23220/25:43976490 - isvavai.cz</a>
Výsledek na webu
<a href="https://ieeexplore.ieee.org/document/11218495" target="_blank" >https://ieeexplore.ieee.org/document/11218495</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.1109/CEIDP61707.2025.11218495" target="_blank" >10.1109/CEIDP61707.2025.11218495</a>
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Influence of Load Impedance on PD Monitoring Sensitivity for High-Voltage Cable Lines
Popis výsledku v původním jazyce
The aim of this paper is to discuss the influence of the load impedance on the sensitivity of partial discharge (PD) measurements. The investigated circuit is based on coupling capacitors to provide a current path for PD signals during resonance testing of cables. The choice of an appropriate value for this capacitance is crucial. However, the overall impedance at the point of measurement is also determined by the inductance of the test circuit. The presented PD measurement method is a nonconventional system using high-frequency current transformers (HFCTs) to measure and localize PD sources along the cable system. The sensitivity of the whole measurement is, among others, strongly dependent on the impedance at the point of measurement. The results of simulations and effective measurements are analyzed and compared. The impact of the different parameters like parasitic capacitances and inductances in the measurement circuit on the accuracy as well as the sensitivity will be discussed in detail.
Název v anglickém jazyce
Influence of Load Impedance on PD Monitoring Sensitivity for High-Voltage Cable Lines
Popis výsledku anglicky
The aim of this paper is to discuss the influence of the load impedance on the sensitivity of partial discharge (PD) measurements. The investigated circuit is based on coupling capacitors to provide a current path for PD signals during resonance testing of cables. The choice of an appropriate value for this capacitance is crucial. However, the overall impedance at the point of measurement is also determined by the inductance of the test circuit. The presented PD measurement method is a nonconventional system using high-frequency current transformers (HFCTs) to measure and localize PD sources along the cable system. The sensitivity of the whole measurement is, among others, strongly dependent on the impedance at the point of measurement. The results of simulations and effective measurements are analyzed and compared. The impact of the different parameters like parasitic capacitances and inductances in the measurement circuit on the accuracy as well as the sensitivity will be discussed in detail.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
—
OECD FORD obor
20201 - Electrical and electronic engineering
Návaznosti výsledku
Projekt
—
Návaznosti
S - Specificky vyzkum na vysokych skolach
Ostatní
Rok uplatnění
2025
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
2025 IEEE Conference on Electrical Insulation and Dielectric Phenomena (CEIDP)
ISBN
979-8-3315-8902-8
ISSN
0084-9162
e-ISSN
2576-2397
Počet stran výsledku
5
Strana od-do
659-663
Název nakladatele
IEEE
Místo vydání
Piscataway
Místo konání akce
Manchester, UK
Datum konání akce
14. 9. 2025
Typ akce podle státní příslušnosti
WRD - Celosvětová akce
Kód UT WoS článku
—