Jednobodový reléový identifikační experiment na základě filtru s konstantní fází
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F49777513%3A23520%2F08%3A00500011" target="_blank" >RIV/49777513:23520/08:00500011 - isvavai.cz</a>
Výsledek na webu
—
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
One point relay identification experiment based on constant-phase filter
Popis výsledku v původním jazyce
Using standard relay identification methods, one obtains a critical frequency response point with the phase shift $-180$ degrees. Such phase is not optimal for consequential PI(D) controller design especially when there is no additional knowledge about the process (e.g. static gain). Currently, an adaptive filter is used to get a frequency response sample with different phase shift. Adaptive filter parameters are tuned during the identification experiment. Unfortunately, the adaptation makes the experiment more time consuming. This paper presents a new low-order filter providing arbitrary constant phase at about three decades. Such filter embedded into relay tuner shortens the experiment significantly. Further, the paper discusses several implementation aspect. The authors believe that presented approach may lead to improvement of existing relay autotuners
Název v anglickém jazyce
One point relay identification experiment based on constant-phase filter
Popis výsledku anglicky
Using standard relay identification methods, one obtains a critical frequency response point with the phase shift $-180$ degrees. Such phase is not optimal for consequential PI(D) controller design especially when there is no additional knowledge about the process (e.g. static gain). Currently, an adaptive filter is used to get a frequency response sample with different phase shift. Adaptive filter parameters are tuned during the identification experiment. Unfortunately, the adaptation makes the experiment more time consuming. This paper presents a new low-order filter providing arbitrary constant phase at about three decades. Such filter embedded into relay tuner shortens the experiment significantly. Further, the paper discusses several implementation aspect. The authors believe that presented approach may lead to improvement of existing relay autotuners
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
BC - Teorie a systémy řízení
OECD FORD obor
—
Návaznosti výsledku
Projekt
<a href="/cs/project/FI-IM3%2F056" target="_blank" >FI-IM3/056: Metody a algoritmy automatického nastavování průmyslových regulátorů a jejich implementace do řídicího systému ZAT-Plant Suite MP.</a><br>
Návaznosti
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)
Ostatní
Rok uplatnění
2008
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
Process Control 2008
ISBN
978-80-7395-077-4
ISSN
—
e-ISSN
—
Počet stran výsledku
9
Strana od-do
—
Název nakladatele
University of Pardubice
Místo vydání
Pardubice
Místo konání akce
Kouty nad Desnou
Datum konání akce
12. 6. 2008
Typ akce podle státní příslušnosti
EUR - Evropská akce
Kód UT WoS článku
—