Results of operational verification of vertical ground heat exchangers
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F60460709%3A41310%2F17%3A73913" target="_blank" >RIV/60460709:41310/17:73913 - isvavai.cz</a>
Nalezeny alternativní kódy
RIV/68407700:21720/17:00313630
Výsledek na webu
<a href="http://dx.doi.org/10.1016/j.enbuild.2017.07.015" target="_blank" >http://dx.doi.org/10.1016/j.enbuild.2017.07.015</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.1016/j.enbuild.2017.07.015" target="_blank" >10.1016/j.enbuild.2017.07.015</a>
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Results of operational verification of vertical ground heat exchangers
Popis výsledku v původním jazyce
This article is devoted to verification of VGHEs (Vertical Ground Heat Exchangers) used as a lowtemperature energy source for heat pumps. The aim and objective of the study was to obtain practical knowledge oftemperatures of rock mass and heattransfer fluids which affectthe life cycle ofthe low temperature sources and the effectiveness of heat pump systems. The objective was also to gain knowledge of specific thermal energy and power extracted by these exchangers which are relevant to the evaluation of frequently used configurations of VGHEs. The results of the operational tests of two active boreholes with different arrangements, namely a single U exchanger (A), a double U exchanger (B) and the reference (inactive) borehole (R). The tests were performed in the years 2012/2014 and involved 2 heating seasons and 2 exchanger stagnation periods. Results of the tests showed that exchanger B is more effective than exchanger A in terms of temperatures and particularly specific heat power and energies.
Název v anglickém jazyce
Results of operational verification of vertical ground heat exchangers
Popis výsledku anglicky
This article is devoted to verification of VGHEs (Vertical Ground Heat Exchangers) used as a lowtemperature energy source for heat pumps. The aim and objective of the study was to obtain practical knowledge oftemperatures of rock mass and heattransfer fluids which affectthe life cycle ofthe low temperature sources and the effectiveness of heat pump systems. The objective was also to gain knowledge of specific thermal energy and power extracted by these exchangers which are relevant to the evaluation of frequently used configurations of VGHEs. The results of the operational tests of two active boreholes with different arrangements, namely a single U exchanger (A), a double U exchanger (B) and the reference (inactive) borehole (R). The tests were performed in the years 2012/2014 and involved 2 heating seasons and 2 exchanger stagnation periods. Results of the tests showed that exchanger B is more effective than exchanger A in terms of temperatures and particularly specific heat power and energies.
Klasifikace
Druh
J<sub>imp</sub> - Článek v periodiku v databázi Web of Science
CEP obor
—
OECD FORD obor
20704 - Energy and fuels
Návaznosti výsledku
Projekt
<a href="/cs/project/LO1605" target="_blank" >LO1605: Univerzitní centrum energeticky efektivních budov – Fáze udržitelnosti</a><br>
Návaznosti
S - Specificky vyzkum na vysokych skolach
Ostatní
Rok uplatnění
2017
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název periodika
ENERGY AND BUILDINGS
ISSN
0378-7788
e-ISSN
1872-6178
Svazek periodika
2017
Číslo periodika v rámci svazku
152
Stát vydavatele periodika
CZ - Česká republika
Počet stran výsledku
9
Strana od-do
185-193
Kód UT WoS článku
000411545100018
EID výsledku v databázi Scopus
2-s2.0-85025696635