Validation of vertical ground heat exchanger design methodologies
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F61989100%3A27120%2F15%3A86094506" target="_blank" >RIV/61989100:27120/15:86094506 - isvavai.cz</a>
Výsledek na webu
<a href="http://www.tandfonline.com/doi/abs/10.1080/10789669.2014.974478?journalCode=uhvc21" target="_blank" >http://www.tandfonline.com/doi/abs/10.1080/10789669.2014.974478?journalCode=uhvc21</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.1080/10789669.2014.974478" target="_blank" >10.1080/10789669.2014.974478</a>
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Validation of vertical ground heat exchanger design methodologies
Popis výsledku v původním jazyce
This work presents a validation of two common methods for designing vertical ground heat exchangers. Both a simulation-based design tool and the ASHRAE handbook design equation are used to find design lengths for four different real systems, using actualexperimental data, including building loads as well as physical parameters as inputs. The measured minimum and maximum ground heat exchanger exiting fluid temperatures were used as the design constraint. The simulation-based design tool predicted the borehole length to within 6% in all cases, while the ASHRAE handbook design equation yielded systems with errors from -21% to 167%. Most of this error can be explained by the way loads are represented in the ASHRAE handbook equation, with differences in the borehole thermal resistance also playing a smaller part. The ASHRAE handbook equation relies on a very simple load representation; although this allows it to be used as a simple hand calculation, it also precludes it achieving acceptabl
Název v anglickém jazyce
Validation of vertical ground heat exchanger design methodologies
Popis výsledku anglicky
This work presents a validation of two common methods for designing vertical ground heat exchangers. Both a simulation-based design tool and the ASHRAE handbook design equation are used to find design lengths for four different real systems, using actualexperimental data, including building loads as well as physical parameters as inputs. The measured minimum and maximum ground heat exchanger exiting fluid temperatures were used as the design constraint. The simulation-based design tool predicted the borehole length to within 6% in all cases, while the ASHRAE handbook design equation yielded systems with errors from -21% to 167%. Most of this error can be explained by the way loads are represented in the ASHRAE handbook equation, with differences in the borehole thermal resistance also playing a smaller part. The ASHRAE handbook equation relies on a very simple load representation; although this allows it to be used as a simple hand calculation, it also precludes it achieving acceptabl
Klasifikace
Druh
J<sub>x</sub> - Nezařazeno - Článek v odborném periodiku (Jimp, Jsc a Jost)
CEP obor
JN - Stavebnictví
OECD FORD obor
—
Návaznosti výsledku
Projekt
—
Návaznosti
V - Vyzkumna aktivita podporovana z jinych verejnych zdroju
Ostatní
Rok uplatnění
2015
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název periodika
Science and Technology for the Built Environment
ISSN
2374-4731
e-ISSN
—
Svazek periodika
21
Číslo periodika v rámci svazku
2
Stát vydavatele periodika
US - Spojené státy americké
Počet stran výsledku
13
Strana od-do
137-149
Kód UT WoS článku
000362067600004
EID výsledku v databázi Scopus
2-s2.0-84925451630