Dispersion Conditions of Combustible Dusts for Determination of Minimum Ignition Energy (MIE)
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F61989100%3A27200%2F14%3A86093125" target="_blank" >RIV/61989100:27200/14:86093125 - isvavai.cz</a>
Výsledek na webu
—
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Dispersion Conditions of Combustible Dusts for Determination of Minimum Ignition Energy (MIE)
Popis výsledku v původním jazyce
The minimum ignition energy (MIE) is an important fi retechnical characteristic which is linked to the sensitivity of a sample to be ignited by electrical spark. Nowadays, this value is determined in accordance with a standard EN 13821 Potentially explosive atmospheres - Explosion prevention and protection - Determination of minimum ignition energy of dust/air mixtures. Most often modifi ed Hartmann tube with volume of 1.2 l and with 7 bar of dispersion pressure is used for determination of MIE. In thispaper, it is discussed whether single value of dispersion pressure is accurate for all kinds of dust. From already done tests it can be derived that dusts with lower bulk density are pushed out of the test vessel and desired homogeneous dust cloud is not created. This hypothesis will be examined by further tests.
Název v anglickém jazyce
Dispersion Conditions of Combustible Dusts for Determination of Minimum Ignition Energy (MIE)
Popis výsledku anglicky
The minimum ignition energy (MIE) is an important fi retechnical characteristic which is linked to the sensitivity of a sample to be ignited by electrical spark. Nowadays, this value is determined in accordance with a standard EN 13821 Potentially explosive atmospheres - Explosion prevention and protection - Determination of minimum ignition energy of dust/air mixtures. Most often modifi ed Hartmann tube with volume of 1.2 l and with 7 bar of dispersion pressure is used for determination of MIE. In thispaper, it is discussed whether single value of dispersion pressure is accurate for all kinds of dust. From already done tests it can be derived that dusts with lower bulk density are pushed out of the test vessel and desired homogeneous dust cloud is not created. This hypothesis will be examined by further tests.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
AQ - Bezpečnost a ochrana zdraví, člověk – stroj
OECD FORD obor
—
Návaznosti výsledku
Projekt
<a href="/cs/project/VG20102015059" target="_blank" >VG20102015059: Vliv teroristického útoku na vybrané průmyslové technologie s nebezpečím výbuchu prachu</a><br>
Návaznosti
S - Specificky vyzkum na vysokych skolach
Ostatní
Rok uplatnění
2014
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
Požární ochrana 2014 : sborník přednášek XXIII. ročníku mezinárodní konference
ISBN
978-80-7385-148-4
ISSN
1803-1803
e-ISSN
—
Počet stran výsledku
4
Strana od-do
79-82
Název nakladatele
Sdružení požárního a bezpečnostního inženýrství
Místo vydání
Ostrava
Místo konání akce
Ostrava
Datum konání akce
3. 9. 2014
Typ akce podle státní příslušnosti
WRD - Celosvětová akce
Kód UT WoS článku
—