Control Circuit of the Heat Exchanger and its Verification on Real Operation Data
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F61989100%3A27240%2F11%3A86080803" target="_blank" >RIV/61989100:27240/11:86080803 - isvavai.cz</a>
Výsledek na webu
—
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Control Circuit of the Heat Exchanger and its Verification on Real Operation Data
Popis výsledku v původním jazyce
The paper deals with the description of the control circuit of the power plant output superheater. Presented control circuit is modeled based on documentation provided by a power plant operator. Its verification is done through testing the mathematical model with real measured operational data. Output power plant superheater is described by a set of partial differential equations of the first order. These equations describe heat exchange between media through a wall with unspecified proportions. Equations are assigned into Simulink S-functions. The Simulink models act as mathematical model of the set consisting of the heat exchangers, on which the experiments are carried out. Actuating device of the regulating circuit is mathematical model of the injection water/steam which keeps the required temperature of the steam at the superheater output. This injection is also implemented as S-function in Simulink.
Název v anglickém jazyce
Control Circuit of the Heat Exchanger and its Verification on Real Operation Data
Popis výsledku anglicky
The paper deals with the description of the control circuit of the power plant output superheater. Presented control circuit is modeled based on documentation provided by a power plant operator. Its verification is done through testing the mathematical model with real measured operational data. Output power plant superheater is described by a set of partial differential equations of the first order. These equations describe heat exchange between media through a wall with unspecified proportions. Equations are assigned into Simulink S-functions. The Simulink models act as mathematical model of the set consisting of the heat exchangers, on which the experiments are carried out. Actuating device of the regulating circuit is mathematical model of the injection water/steam which keeps the required temperature of the steam at the superheater output. This injection is also implemented as S-function in Simulink.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
JE - Nejaderná energetika, spotřeba a užití energie
OECD FORD obor
—
Návaznosti výsledku
Projekt
<a href="/cs/project/GA102%2F09%2F1003" target="_blank" >GA102/09/1003: Modelování vysokoteplotních výměníků tepla a využití modelů pro optimální regulaci výměníků</a><br>
Návaznosti
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)
Ostatní
Rok uplatnění
2011
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
Proceedings of 2011 IEEE 16th Conference on Emerging Technologies and Factory Automation
ISBN
978-1-4577-0018-7
ISSN
1946-0759
e-ISSN
—
Počet stran výsledku
7
Strana od-do
1-7
Název nakladatele
Institute of Electrical and Electronics Engineers
Místo vydání
New York
Místo konání akce
Toulouse
Datum konání akce
5. 9. 2011
Typ akce podle státní příslušnosti
WRD - Celosvětová akce
Kód UT WoS článku
000297542900074