Regulation Of The Reactive Power Of A WEC Using The ASRU Application On MV Level
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F61989100%3A27240%2F17%3A10238258" target="_blank" >RIV/61989100:27240/17:10238258 - isvavai.cz</a>
Výsledek na webu
<a href="http://ieeexplore.ieee.org/document/7967254/" target="_blank" >http://ieeexplore.ieee.org/document/7967254/</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.1109/EPE.2017.7967254" target="_blank" >10.1109/EPE.2017.7967254</a>
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Regulation Of The Reactive Power Of A WEC Using The ASRU Application On MV Level
Popis výsledku v původním jazyce
This paper is focused on challenges related to an increased quantity of distribution energy resources connected to the distribution network within the context of newly defined requirements ENTSO-E, follow-up European standards TS 50549 and codes of distribution system operators on regulation of voltage through control of the reactive power in terms of P-Q diagram. A high number of connected and operated distribution energy resources results in changes in quality parameters of voltage in a distribution grid. The evaluation of the measured parameters enables to detect overvoltage or voltage fluctuations that are not in accordance with requirements of EN 50160 standard. This paper describes courses of voltage during operation of a wind energy converter (WEC) operated in parallel with the CEZ Distribuce distribution network (DN) on medium voltage (MV) level with the prescribed control of the reactive power to a fixed value of a power factor and the control of the reactive power depending on voltage. The measurement results of U, P, Q values evaluate an influence of the voltage reactive power in a point of connection of a power generating plant to the grid with regard to keeping the voltage within a range of operating limits.
Název v anglickém jazyce
Regulation Of The Reactive Power Of A WEC Using The ASRU Application On MV Level
Popis výsledku anglicky
This paper is focused on challenges related to an increased quantity of distribution energy resources connected to the distribution network within the context of newly defined requirements ENTSO-E, follow-up European standards TS 50549 and codes of distribution system operators on regulation of voltage through control of the reactive power in terms of P-Q diagram. A high number of connected and operated distribution energy resources results in changes in quality parameters of voltage in a distribution grid. The evaluation of the measured parameters enables to detect overvoltage or voltage fluctuations that are not in accordance with requirements of EN 50160 standard. This paper describes courses of voltage during operation of a wind energy converter (WEC) operated in parallel with the CEZ Distribuce distribution network (DN) on medium voltage (MV) level with the prescribed control of the reactive power to a fixed value of a power factor and the control of the reactive power depending on voltage. The measurement results of U, P, Q values evaluate an influence of the voltage reactive power in a point of connection of a power generating plant to the grid with regard to keeping the voltage within a range of operating limits.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
—
OECD FORD obor
20201 - Electrical and electronic engineering
Návaznosti výsledku
Projekt
—
Návaznosti
S - Specificky vyzkum na vysokych skolach
Ostatní
Rok uplatnění
2017
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
EPE 2017 : proceedings of the 18th international scientific conference on electric power engineering : May 17-19, 2017, Kouty nad Desnou, Czech Republic
ISBN
978-1-5090-6406-9
ISSN
2376-5623
e-ISSN
neuvedeno
Počet stran výsledku
5
Strana od-do
272-276
Název nakladatele
IEEE
Místo vydání
Piscataway
Místo konání akce
Kouty nad Desnou
Datum konání akce
17. 5. 2017
Typ akce podle státní příslušnosti
WRD - Celosvětová akce
Kód UT WoS článku
000422921000051